Skip to main content
Schneider Electric C11B3TM032B — Miniature Circuit Breakers (MCB)

C11B3TM032B ComPacT NSXm 3P 32A TM-D Circuit Breaker, 25 kA

MPNC11B3TM032B
Active

Schneider Electric ComPacT NSXm, C11B3TM032B, 3P circuit breaker, 32 A (40 °C), TM-D thermal-magnetic trip unit, 25 kA at 415 V AC, IP40, grey RAL 7016.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

C11B3TM032B — Identification
ParameterValue
Product nameComPacT NSXm
Product rangeComPacT
Product/component typeCircuit breaker
Device applicationDistribution
C11B3TM032B — Ratings
ParameterValue
Rated current (In)32 A at 40 °C
Poles configuration3P
Rated operational voltage (Ue)690 V AC 50/60 Hz
Rated insulation voltage (Ui)800 V AC 50/60 Hz
Rated impulse withstand voltage (Uimp)8 kV
Network type (AC/DC)AC
Network frequency50/60 Hz
Utilisation categoryCategory A
Overvoltage categoryIII
C11B3TM032B — Protection
ParameterValue
Trip unit technologyThermal-magnetic
Earth-leakage protectionWithout
Suitability for isolationYes conforming to IEC 60947-2
Electrical durability (cycles)20000 cycles at 440 V In/2 10000 cycles at 440 V In 10000 cycles at 690 V In/2 5000 cycles at 690 V In
Mechanical durability (cycles)20000 cycles
C11B3TM032B — Mechanical
ParameterValue
Mounting supportBackplate
Control typeToggle
Local signalling/indicationFlag (green) for presence of auxiliary contacts
Number of 9 mm pitches9 module
C11B3TM032B — Environmental
ParameterValue
Operating ambient temperature-25...70 °C
Storage ambient temperature-50...85 °C
IP degree of protectionIP40 conforming to IEC 60529
Pollution degree3 conforming to IEC 60664-1
Relative humidity0...95 %
C11B3TM032B — Approvals
ParameterValue
StandardsEN/IEC 60947-2
C11B3TM032B — Electrical
ParameterValue
[Icu] rated ultimate short-circuit breaking capacity50 kA Icu at 220...240 V AC 50/60 Hz conforming to IEC 60947-2 25 kA Icu at 380...415 V AC 50/60 Hz conforming to IEC 60947-2 20 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 10 kA Icu at 500 V AC 50/60 Hz conforming to IEC 60947-2
[Ics] rated service short-circuit breaking capacity50 kA at 220...240 V AC 50/60 Hz conforming to IEC 60947-2 25 kA at 380...415 V AC 50/60 Hz conforming to IEC 60947-2 20 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2 10 kA at 500 V AC 50/60 Hz conforming to IEC 60947-2
C11B3TM032B — Specifications
ParameterValue
[Ir] long-time protection pick-up adjustment range0.7...1 x In
Trip unit protection functionsLI

Product details

The Schneider Electric C11B3TM032B is a ComPacT NSXm 3-pole circuit breaker with a TM-D thermal-magnetic trip unit rated 32 A at 40 °C. It is designed for distribution applications per EN/IEC 60947-2, with a breaking capacity of 25 kA at 415 V AC (performance level B). The 32 A rating at 40 °C means the breaker carries its full rated current in a 40 °C ambient — no derating needed at typical panel temperatures.

The 9-module pitch (9 x 9 mm = 81 mm width) fits standard DIN-rail enclosures. Connection is front-facing via compression lugs or busbars; connection pitch is 35 mm with spreaders, 27 mm without. IP40 front protection means it is sealed against tools and small objects — suitable for enclosed panel installation, not washdown areas.

Frequently asked questions

What is the breaking capacity of C11B3TM032B?

The C11B3TM032B has a breaking capacity of 25 kA at 415 V AC (performance level B per EN/IEC 60947-2). This is the maximum fault current it can safely interrupt at that voltage.

What trip unit does C11B3TM032B use?

It uses a TM-D thermal-magnetic trip unit rated 32 A at 40 °C. The thermal element protects against overload; the magnetic element provides short-circuit protection.

Where can I buy C11B3TM032B?

The C11B3TM032B is sourced to order against an RFQ through independent distribution. Submit a request for quote to confirm current availability and pricing.

MPN
C11B3TM032B