Skip to main content
Schneider Electric C11B3TM063B — Miniature Circuit Breakers (MCB)

C11B3TM063B Schneider ComPacT NSXm 63A 3P Thermal-Magnetic M

MPNC11B3TM063B
Active

Schneider Electric, ComPacT NSXm, C11B3TM063B, 63 A 3P thermal-magnetic circuit breaker, 25 kA at 415 V AC, EN/IEC 60947-2, IP40.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

C11B3TM063B — Identification
ParameterValue
Product nameComPacT NSXm
Product rangeComPacT
Product/component typeCircuit breaker
Device applicationDistribution
C11B3TM063B — Ratings
ParameterValue
Rated current (In)63 A at 40 °C
Poles configuration3P
Rated operational voltage (Ue)690 V AC 50/60 Hz
Rated insulation voltage (Ui)800 V AC 50/60 Hz
Rated impulse withstand voltage (Uimp)8 kV
Network type (AC/DC)AC
Network frequency50/60 Hz
Utilisation categoryCategory A
Overvoltage categoryIII
C11B3TM063B — Protection
ParameterValue
Trip unit technologyThermal-magnetic
Earth-leakage protectionWithout
Suitability for isolationYes conforming to IEC 60947-2
Electrical durability (cycles)20000 cycles at 440 V In/2 10000 cycles at 440 V In 10000 cycles at 690 V In/2 5000 cycles at 690 V In
Mechanical durability (cycles)20000 cycles
C11B3TM063B — Mechanical
ParameterValue
Mounting supportBackplate
Control typeToggle
Local signalling/indicationFlag (green) for presence of auxiliary contacts
Number of 9 mm pitches9 module
C11B3TM063B — Environmental
ParameterValue
Operating ambient temperature-25...70 °C
Storage ambient temperature-50...85 °C
IP degree of protectionIP40 conforming to IEC 60529
Pollution degree3 conforming to IEC 60664-1
Relative humidity0...95 %
C11B3TM063B — Approvals
ParameterValue
StandardsEN/IEC 60947-2
C11B3TM063B — Electrical
ParameterValue
[Icu] rated ultimate short-circuit breaking capacity50 kA Icu at 220...240 V AC 50/60 Hz conforming to IEC 60947-2 25 kA Icu at 380...415 V AC 50/60 Hz conforming to IEC 60947-2 20 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 10 kA Icu at 500 V AC 50/60 Hz conforming to IEC 60947-2
[Ics] rated service short-circuit breaking capacity50 kA at 220...240 V AC 50/60 Hz conforming to IEC 60947-2 25 kA at 380...415 V AC 50/60 Hz conforming to IEC 60947-2 20 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2 10 kA at 500 V AC 50/60 Hz conforming to IEC 60947-2
C11B3TM063B — Specifications
ParameterValue
[Ir] long-time protection pick-up adjustment range0.7...1 x In
Trip unit protection functionsLI

Product details

The C11B3TM063B is a Schneider Electric ComPacT NSXm 63 A three-pole thermal-magnetic circuit breaker. It carries a 25 kA breaking capacity at 415 V AC (performance level B), enough for most distribution panelboard applications where fault currents stay under that threshold. The TM-D trip unit is fixed thermal-magnetic — no interchangeable electronic trip module, so the 63 A rating at 40 °C is what you spec into the BOM.

What the ratings mean for fit

The 25 kA at 415 V AC is the interrupting rating — it guarantees the breaker clears a fault up to that level without welding contacts or rupturing the case. Below that, it coordinates with downstream branch breakers. The 63 A thermal-magnetic trip protects against sustained overloads (thermal element) and short-circuits (magnetic instantaneous trip). Category A utilisation means it's not intended for motor-starting duty under IEC 60947-2; it's sized for distribution and feeder circuits. Mounts on a backplate (not DIN rail) with front connections top and bottom. The 9-module pitch at 81 mm wide means it occupies nine 9 mm positions in a panel. IP40 enclosure protection keeps dust out but not water — indoor panel use only.

Sourcing and lifecycle

Current-production lifecycle stage. Active catalogue item from Schneider's ComPacT NSXm family. Sourced and quoted to order against an RFQ through independent distribution.

Standards and approvals

Certified to EN/IEC 60947-2, the low-voltage switchgear standard. Suitability for isolation is confirmed per that standard — you can use it as a visible-break disconnect in a distribution panel. Pollution degree 3 (IEC 60664-1) suits it for industrial environments with conductive dust or condensation. Overvoltage category III covers fixed-installation applications downstream of the utility meter.

Frequently asked questions

What is the breaking capacity of C11B3TM063B?

25 kA at 415 V AC, performance level B. That's the maximum fault current it can safely interrupt at that voltage.

What standards does C11B3TM063B comply with?

EN/IEC 60947-2 for low-voltage switchgear. It also meets pollution degree 3 per IEC 60664-1 and overvoltage category III.

MPN
C11B3TM063B