Schneider Electric C11B6TM025B — Miniature Circuit Breakers (MCB)

Schneider Electric C11B6TM025B ComPacT NSXm 25A 4P MCCB, 25

MPNC11B6TM025B
Active

Schneider Electric ComPacT NSXm, circuit breaker, 4P, 25 A at 40 °C, 25 kA 415 V AC, thermal-magnetic TM-D, IP40, grey (RAL 7016).

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

C11B6TM025B — Identification
ParameterValue
Product nameComPacT NSXm
Product rangeComPacT
Product/component typeCircuit breaker
Device applicationDistribution
C11B6TM025B — Ratings
ParameterValue
Rated current (In)25 A at 40 °C
Poles configuration4P
Rated operational voltage (Ue)690 V AC 50/60 Hz
Rated insulation voltage (Ui)800 V AC 50/60 Hz
Rated impulse withstand voltage (Uimp)8 kV
Network type (AC/DC)AC
Network frequency50/60 Hz
Utilisation categoryCategory A
Overvoltage categoryIII
C11B6TM025B — Protection
ParameterValue
Trip unit technologyThermal-magnetic
Earth-leakage protectionWithout
Suitability for isolationYes conforming to IEC 60947-2
Electrical durability (cycles)20000 cycles at 440 V In/2 10000 cycles at 440 V In 10000 cycles at 690 V In/2 5000 cycles at 690 V In
Mechanical durability (cycles)20000 cycles
C11B6TM025B — Mechanical
ParameterValue
Mounting supportBackplate
Control typeToggle
Local signalling/indicationFlag (green) for presence of auxiliary contacts
Number of 9 mm pitches12 module
C11B6TM025B — Environmental
ParameterValue
Operating ambient temperature-25...70 °C
Storage ambient temperature-50...85 °C
IP degree of protectionIP40 conforming to IEC 60529
Pollution degree3 conforming to IEC 60664-1
Relative humidity0...95 %
C11B6TM025B — Approvals
ParameterValue
StandardsEN/IEC 60947-2
C11B6TM025B — Electrical
ParameterValue
[Icu] rated ultimate short-circuit breaking capacity50 kA Icu at 220...240 V AC 50/60 Hz conforming to IEC 60947-2 25 kA Icu at 380...415 V AC 50/60 Hz conforming to IEC 60947-2 20 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 10 kA Icu at 500 V AC 50/60 Hz conforming to IEC 60947-2
[Ics] rated service short-circuit breaking capacity50 kA at 220...240 V AC 50/60 Hz conforming to IEC 60947-2 25 kA at 380...415 V AC 50/60 Hz conforming to IEC 60947-2 20 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2 10 kA at 500 V AC 50/60 Hz conforming to IEC 60947-2
C11B6TM025B — Specifications
ParameterValue
[Ir] long-time protection pick-up adjustment range0.7...1 x In
Trip unit protection functionsLI

Product details

The Schneider Electric C11B6TM025B is a ComPacT NSXm 63B frame moulded-case circuit breaker (MCCB) with four poles (4P), a thermal-magnetic TM-D trip unit, and a 25 A rating at 40 °C. It's designed for distribution duty in commercial and industrial panels, built to EN/IEC 60947-2.

Integration and mounting — panel fit

The 108 mm width spans 12 module pitches at 9 mm each, so it occupies a predictable footprint in a multi-breaker lineup. Connection terminals accept compression lugs or busbars, front-connected both top and bottom — no rear-access required. Neutral is on the left. IP40 enclosure protection and IK07 impact resistance suit it for enclosed panel mounting where occasional tool contact or debris is a concern.

Frequently asked questions

How do I get current pricing and availability for C11B6TM025B?

The C11B6TM025B is sourced to order against an RFQ through independent distribution. Submit a request for quote; pricing and stock status are confirmed at that time.

What is C11B6TM025B's breaking capacity?

Performance level B: 25 kA at 415 V AC. That's the maximum fault current it can safely interrupt at that voltage without upstream protection needing to clear.

What standards does C11B6TM025B comply with?

It is designed and certified to EN/IEC 60947-2, the standard for low-voltage switchgear and controlgear — specifically for circuit breakers. It also carries suitability for isolation per that standard.

MPN
C11B6TM025B