Skip to main content
Schneider Electric C11B6TM040L — Miniature Circuit Breakers (MCB)

Schneider Electric C11B6TM040L ComPacT NSXm 40A 4P 25kA

MPNC11B6TM040L
Active

Schneider Electric ComPacT NSXm, C11B6TM040L, 4P circuit breaker, 40 A TM-D thermal-magnetic trip, 25 kA at 415 V AC, EN/IEC 60947-2.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

C11B6TM040L — Identification
ParameterValue
Product nameComPacT NSXm
Product rangeComPacT
Product/component typeCircuit breaker
Device applicationDistribution
C11B6TM040L — Ratings
ParameterValue
Rated current (In)40 A at 40 °C
Poles configuration4P
Rated operational voltage (Ue)690 V AC 50/60 Hz
Rated insulation voltage (Ui)800 V AC 50/60 Hz
Rated impulse withstand voltage (Uimp)8 kV
Network type (AC/DC)AC
Network frequency50/60 Hz
Utilisation categoryCategory A
Overvoltage categoryIII
C11B6TM040L — Protection
ParameterValue
Trip unit technologyThermal-magnetic
Earth-leakage protectionWithout
Suitability for isolationYes conforming to IEC 60947-2
Electrical durability (cycles)20000 cycles at 440 V In/2 10000 cycles at 440 V In 10000 cycles at 690 V In/2 5000 cycles at 690 V In
Mechanical durability (cycles)20000 cycles
C11B6TM040L — Mechanical
ParameterValue
Mounting supportBackplate
Control typeToggle
Local signalling/indicationFlag (green) for presence of auxiliary contacts
Number of 9 mm pitches12 module
C11B6TM040L — Environmental
ParameterValue
Operating ambient temperature-25...70 °C
Storage ambient temperature-50...85 °C
IP degree of protectionIP40 conforming to IEC 60529
Pollution degree3 conforming to IEC 60664-1
Relative humidity0...95 %
C11B6TM040L — Approvals
ParameterValue
StandardsEN/IEC 60947-2
C11B6TM040L — Electrical
ParameterValue
[Icu] rated ultimate short-circuit breaking capacity50 kA Icu at 220...240 V AC 50/60 Hz conforming to IEC 60947-2 25 kA Icu at 380...415 V AC 50/60 Hz conforming to IEC 60947-2 20 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 10 kA Icu at 500 V AC 50/60 Hz conforming to IEC 60947-2
[Ics] rated service short-circuit breaking capacity50 kA at 220...240 V AC 50/60 Hz conforming to IEC 60947-2 25 kA at 380...415 V AC 50/60 Hz conforming to IEC 60947-2 20 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2 10 kA at 500 V AC 50/60 Hz conforming to IEC 60947-2
C11B6TM040L — Specifications
ParameterValue
[Ir] long-time protection pick-up adjustment range0.7...1 x In
Trip unit protection functionsLI

Product details

The C11B6TM040L is a Schneider Electric ComPacT NSXm moulded-case circuit breaker, 4-pole (4P), rated 40 A at 40 °C with a TM-D thermal-magnetic trip unit. The EN/IEC 60947-2 standard certifies it for isolation (marked on the device) and overcurrent protection in distribution boards.

Backplate-mounted in a distribution panel, 12-module 9 mm pitch width (108 mm), 137 mm tall, 80 mm deep. Front connections top and bottom — Everlink lugs accept 2.5 to 95 mm² rigid or stranded aluminium/copper, or 2.5 to 70 mm² flexible copper. Neutral on the left. The IP40 enclosure keeps dust out of a clean indoor panel; IK07 impact rating handles accidental tool drops during commissioning.

Electrical durability and operating conditions

Rated for 20,000 mechanical cycles and up to 20,000 electrical cycles at 440 V In/2, derating to 5,000 cycles at 690 V In. Operates at 50/60 Hz, up to 2000 m altitude without derating (5000 m with derating), 0–95 % relative humidity. Overvoltage category III — suitable for fixed-installation distribution boards downstream of the main service entrance.

Frequently asked questions

Who supplies C11B6TM040L and how is it quoted?

Sourced and quoted to order against an RFQ through independent distribution channels; availability and current pricing are confirmed at quote time.

What is C11B6TM040L's breaking capacity?

Performance level B: 25 kA at 415 V AC per EN/IEC 60947-2.

What compliance documentation does this brand provide for C11B6TM040L?

The breaker carries EN/IEC 60947-2 certification for overcurrent protection and isolation suitability; the IP and IK ratings are per IEC 60529 and IEC 62262 respectively. Pollution degree 3 per IEC 60664-1.

MPN