Schneider Electric C11B6TM100B — Miniature Circuit Breakers (MCB)

Schneider Electric C11B6TM100B ComPacT NSXm 100A MCCB, 25kA

MPNC11B6TM100B
Active

Schneider Electric ComPacT NSXm, C11B6TM100B, 4-pole MCCB, 100 A at 40 °C, 25 kA at 415 V AC, thermal-magnetic TM-D trip unit, grey (RAL 7016).

$476.60Ref. price · indicative, final on quote
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

C11B6TM100B — Identification
ParameterValue
Product nameComPacT NSXm
Product rangeComPacT
Product/component typeCircuit breaker
Device applicationDistribution
C11B6TM100B — Ratings
ParameterValue
Rated current (In)100 A at 40 °C
Poles configuration4P
Rated operational voltage (Ue)440 V AC 50/60 Hz
Rated insulation voltage (Ui)800 V AC 50/60 Hz
Rated impulse withstand voltage (Uimp)8 kV
Network type (AC/DC)AC
Network frequency50/60 Hz
Utilisation categoryCategory A
Overvoltage categoryIII
C11B6TM100B — Protection
ParameterValue
Trip unit technologyThermal-magnetic
Earth-leakage protectionWithout
Suitability for isolationYes conforming to IEC 60947-2
Electrical durability (cycles)20000 cycles at 440 V In/2 10000 cycles at 440 V In
Mechanical durability (cycles)20000 cycles
C11B6TM100B — Mechanical
ParameterValue
Mounting supportBackplate
Control typeToggle
Local signalling/indicationFlag (green) for presence of auxiliary contacts
Number of 9 mm pitches12 module
C11B6TM100B — Environmental
ParameterValue
Operating ambient temperature-25...70 °C
Storage ambient temperature-50...85 °C
IP degree of protectionIP40 conforming to IEC 60529
Pollution degree3 conforming to IEC 60664-1
Relative humidity0...95 %
C11B6TM100B — Approvals
ParameterValue
StandardsEN/IEC 60947-2
C11B6TM100B — Electrical
ParameterValue
[Icu] rated ultimate short-circuit breaking capacity50 kA Icu at 220...240 V AC 50/60 Hz conforming to IEC 60947-2 25 kA Icu at 380...415 V AC 50/60 Hz conforming to IEC 60947-2 20 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2
[Ics] rated service short-circuit breaking capacity50 kA at 220...240 V AC 50/60 Hz conforming to IEC 60947-2 25 kA at 380...415 V AC 50/60 Hz conforming to IEC 60947-2 20 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2
C11B6TM100B — Specifications
ParameterValue
[Ir] long-time protection pick-up adjustment range0.7...1 x In
Trip unit protection functionsLI

Product details

Schneider Electric C11B6TM100B is a 4-pole ComPacT NSXm moulded-case circuit breaker rated 100 A at 40 °C with a 25 kA breaking capacity at 415 V AC — that's the interrupting rating you need for a distribution board fed from a transformer of that size, not a motor branch. The thermal-magnetic TM-D trip unit handles overloads and short-circuits in one package, no add-on module needed.

Mount it in a warmer enclosure or next to other heat sources and you'll need to derate — the TM-D thermal element responds to ambient temperature, so a crowded panel at 50 °C might knock that down to 90 A or so. Plan your fill factor accordingly.

The 108 mm width spans 12 module pitches at 9 mm each, so it'll occupy about the same space as twelve single-pole MCBs side by side. Connection terminals accept compression lugs or busbars; front-facing connections on both top and bottom keep the wiring plane accessible for panel builders. Neutral is on the left, which matches the standard busbar layout for most distribution boards. The toggle control gives clear mechanical on/off indication, and the green flag signals when auxiliary contacts are present — handy for a quick visual check without opening the panel door.

Frequently asked questions

What is C11B6TM100B's breaking capacity?

It's rated 25 kA at 415 V AC, performance level B per IEC 60947-2. That's the Icu — the maximum fault current it can safely interrupt once.

What type of trip unit does this breaker use?

A thermal-magnetic TM-D trip unit — thermal element for overload protection, magnetic coil for short-circuit. Fixed settings, no adjustment dial.

Where can I buy C11B6TM100B and what is the lead time?

This part is sourced and quoted to order against an RFQ through independent distribution channels. Availability and current pricing are confirmed at quote time.

What compliance documentation is available for C11B6TM100B?

The breaker is certified to EN/IEC 60947-2 and IEC 60664-1 (pollution degree 3). Standard Schneider documentation includes the declaration of conformity; RoHS and REACH compliance data is available on request.