C11E3TM016B — Identification
ParameterValue
Product nameComPacT NSXm
Product rangeComPacT
Product/component typeCircuit breaker
Device applicationDistribution
C11E3TM016B — Ratings
ParameterValue
Rated current (In)16 A at 40 °C
Poles configuration3P
Rated operational voltage (Ue)690 V AC 50/60 Hz
Rated insulation voltage (Ui)800 V AC 50/60 Hz
Rated impulse withstand voltage (Uimp)8 kV
Network type (AC/DC)AC
Network frequency50/60 Hz
Utilisation categoryCategory A
Overvoltage categoryIII
C11E3TM016B — Protection
ParameterValue
Trip unit technologyThermal-magnetic
Earth-leakage protectionWithout
Suitability for isolationYes conforming to IEC 60947-2
Electrical durability (cycles)20000 cycles at 440 V In/2 10000 cycles at 440 V In 10000 cycles at 690 V In/2 5000 cycles at 690 V In
Mechanical durability (cycles)20000 cycles
C11E3TM016B — Mechanical
ParameterValue
Mounting supportBackplate
Control typeToggle
Local signalling/indicationFlag (green) for presence of auxiliary contacts
Number of 9 mm pitches9 module
C11E3TM016B — Environmental
ParameterValue
Operating ambient temperature-25...70 °C
Storage ambient temperature-50...85 °C
IP degree of protectionIP40 conforming to IEC 60529
Pollution degree3 conforming to IEC 60664-1
Relative humidity0...95 %
C11E3TM016B — Approvals
ParameterValue
StandardsEN/IEC 60947-2
C11E3TM016B — Electrical
ParameterValue
[Icu] rated ultimate short-circuit breaking capacity25 kA Icu at 220...240 V AC 50/60 Hz conforming to IEC 60947-2 16 kA Icu at 380...415 V AC 50/60 Hz conforming to IEC 60947-2 10 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 8 kA Icu at 500 V AC 50/60 Hz conforming to IEC 60947-2
[Ics] rated service short-circuit breaking capacity25 kA at 220...240 V AC 50/60 Hz conforming to IEC 60947-2 16 kA at 380...415 V AC 50/60 Hz conforming to IEC 60947-2 10 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2 8 kA at 500 V AC 50/60 Hz conforming to IEC 60947-2
C11E3TM016B — Specifications
ParameterValue
[Ir] long-time protection pick-up adjustment range0.7...1 x In
Trip unit protection functionsLI

Product details

ComPacT NSXm 16 A MCCB, 3-pole, TM-D trip

Mounts on a backplate, front-connected top and bottom. Accepts compression lugs or busbars. 9-module pitch at 81 mm wide, 137 mm high, 80 mm deep. IP40 enclosure protection, IK07 impact resistance.

Electrical durability and environmental ratings

Rated for 20,000 mechanical cycles. Electrical endurance depends on load: 20,000 cycles at 440 V at half rated current, 10,000 cycles at full rated current (440 V), and 5,000 cycles at 690 V at full rated current. Power dissipation is 2.3 W per pole. Relative humidity range 0–95 %. Suitable for horizontal or vertical mounting flat on the back.

Frequently asked questions

What is the breaking capacity of C11E3TM016B?

The C11E3TM016B has a breaking capacity of 16 kA at 415 V AC, performance level E, per EN/IEC 60947-2.