The 4P configuration with neutral left handles three-phase plus neutral distribution boards common in European panel builds.
Lifecycle stage is current. It is still in Schneider's active catalogue, so you can spec it for a new panel design or a BOM line.
The 9 mm pitch takes 12 modules, so it fits standard DIN-rail enclosure cutouts. Front terminals (Everlink lugs) accept 2.5–95 mm² rigid or stranded aluminium/copper, or 2.5–70 mm² flexible copper — that's a wide enough lug range to land feeder cables from a 25 A bus without adaptors. IP40 front face, IK07 impact resistance.
Electrical durability: 20,000 cycles at 440 V at half rated current (In/2), 10,000 cycles at 440 V at full In, and 5,000 cycles at 690 V at full In. That's a solid mechanical life for a distribution breaker — it'll outlast most panel refreshes.