Mounts on a backplate in either horizontal or vertical orientation, flat on the back. The 108 mm width and 137 mm height fit standard panel layouts. Connection terminals accept compression lugs or busbars from the front on both line and load sides. Neutral is on the left. The IP40 enclosure and IK07 impact resistance suit indoor panel environments — no washdown rating, so keep it inside the cabinet.
Schneider Electric C11H4TM040B ComPacT NSXm 40A 4P MCCB, 70
MPNC11H4TM040B
Active
Schneider Electric ComPacT NSXm, C11H4TM040B, 4P thermal-magnetic MCCB, 40 A at 40 °C, 70 kA at 415 V AC, EN/IEC 60947-2.
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026
Specifications
| Parameter | Value |
|---|---|
| Product name | ComPacT NSXm |
| Product range | ComPacT |
| Product/component type | Circuit breaker |
| Device application | Distribution |
| Parameter | Value |
|---|---|
| Rated current (In) | 40 A at 40 °C |
| Poles configuration | 4P |
| Rated operational voltage (Ue) | 690 V AC 50/60 Hz |
| Rated insulation voltage (Ui) | 800 V AC 50/60 Hz |
| Rated impulse withstand voltage (Uimp) | 8 kV |
| Network type (AC/DC) | AC |
| Network frequency | 50/60 Hz |
| Utilisation category | Category A |
| Overvoltage category | III |
| Parameter | Value |
|---|---|
| Trip unit technology | Thermal-magnetic |
| Earth-leakage protection | Without |
| Suitability for isolation | Yes conforming to IEC 60947-2 |
| Electrical durability (cycles) | 20000 cycles at 440 V In/2 10000 cycles at 440 V In 10000 cycles at 690 V In/2 5000 cycles at 690 V In |
| Mechanical durability (cycles) | 20000 cycles |
| Parameter | Value |
|---|---|
| Mounting support | Backplate |
| Control type | Toggle |
| Local signalling/indication | Flag (green) for presence of auxiliary contacts |
| Number of 9 mm pitches | 12 module |
| Parameter | Value |
|---|---|
| Operating ambient temperature | -25...70 °C |
| Storage ambient temperature | -50...85 °C |
| IP degree of protection | IP40 conforming to IEC 60529 |
| Pollution degree | 3 conforming to IEC 60664-1 |
| Relative humidity | 0...95 % |
| Parameter | Value |
|---|---|
| Standards | EN/IEC 60947-2 |
| Parameter | Value |
|---|---|
| [Icu] rated ultimate short-circuit breaking capacity | 100 kA Icu at 220...240 V AC 50/60 Hz conforming to IEC 60947-2 70 kA Icu at 380...415 V AC 50/60 Hz conforming to IEC 60947-2 65 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 30 kA Icu at 500 V AC 50/60 Hz conforming to IEC 60947-2 22 kA Icu at 525 V AC 50/60 Hz conforming to IEC 60947-2 10 kA Icu at 660...690 V AC 50/60 Hz conforming to IEC 60947-2 |
| [Ics] rated service short-circuit breaking capacity | 100 kA at 220...240 V AC 50/60 Hz conforming to IEC 60947-2 70 kA at 380...415 V AC 50/60 Hz conforming to IEC 60947-2 65 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2 30 kA at 500 V AC 50/60 Hz conforming to IEC 60947-2 22 kA at 525 V AC 50/60 Hz conforming to IEC 60947-2 2.5 kA at 660...690 V AC 50/60 Hz conforming to IEC 60947-2 |
| Parameter | Value |
|---|---|
| [Ir] long-time protection pick-up adjustment range | 0.7...1 x In |
| Trip unit protection functions | LI |
Product details
Frequently asked questions
What is the closest pin-compatible alternative to C11H4TM040B in this component family?
Within the ComPacT NSXm range, the primary difference is the trip unit rating. A 63 A frame (NSXm 63H) shares the same physical footprint and terminal layout; the trip unit rating determines the continuous current. No pin-compatible alternative with a different trip technology is listed for this frame.