Skip to main content
Schneider Electric C11N4TM016B — Miniature Circuit Breakers (MCB)

C11N4TM016B ComPacT NSXm 16A 4P Thermal-Magnetic, 50 kA

MPNC11N4TM016B
Active

Schneider Electric ComPacT NSXm, 4P, 16 A, TM-D thermal-magnetic trip, 50 kA at 415 V AC, EN/IEC 60947-2.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

C11N4TM016B — Identification
ParameterValue
Product nameComPacT NSXm
Product rangeComPacT
Product/component typeCircuit breaker
Device applicationDistribution
C11N4TM016B — Ratings
ParameterValue
Rated current (In)16 A at 40 °C
Poles configuration4P
Rated operational voltage (Ue)690 V AC 50/60 Hz
Rated insulation voltage (Ui)800 V AC 50/60 Hz
Rated impulse withstand voltage (Uimp)8 kV
Network type (AC/DC)AC
Network frequency50/60 Hz
Utilisation categoryCategory A
Overvoltage categoryIII
C11N4TM016B — Protection
ParameterValue
Trip unit technologyThermal-magnetic
Earth-leakage protectionWithout
Suitability for isolationYes conforming to IEC 60947-2
Electrical durability (cycles)20000 cycles at 440 V In/2 10000 cycles at 440 V In 10000 cycles at 690 V In/2 5000 cycles at 690 V In
Mechanical durability (cycles)20000 cycles
C11N4TM016B — Mechanical
ParameterValue
Mounting supportBackplate
Control typeToggle
Local signalling/indicationFlag (green) for presence of auxiliary contacts
Number of 9 mm pitches12 module
C11N4TM016B — Environmental
ParameterValue
Operating ambient temperature-25...70 °C
Storage ambient temperature-50...85 °C
IP degree of protectionIP40 conforming to IEC 60529
Pollution degree3 conforming to IEC 60664-1
Relative humidity0...95 %
C11N4TM016B — Approvals
ParameterValue
StandardsEN/IEC 60947-2
C11N4TM016B — Electrical
ParameterValue
[Icu] rated ultimate short-circuit breaking capacity90 kA Icu at 220...240 V AC 50/60 Hz conforming to IEC 60947-2 50 kA Icu at 380...415 V AC 50/60 Hz conforming to IEC 60947-2 50 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 25 kA Icu at 500 V AC 50/60 Hz conforming to IEC 60947-2 15 kA Icu at 525 V AC 50/60 Hz conforming to IEC 60947-2 10 kA Icu at 660...690 V AC 50/60 Hz conforming to IEC 60947-2
[Ics] rated service short-circuit breaking capacity90 kA at 220...240 V AC 50/60 Hz conforming to IEC 60947-2 50 kA at 380...415 V AC 50/60 Hz conforming to IEC 60947-2 50 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2 25 kA at 500 V AC 50/60 Hz conforming to IEC 60947-2 15 kA at 525 V AC 50/60 Hz conforming to IEC 60947-2 2.5 kA at 660...690 V AC 50/60 Hz conforming to IEC 60947-2
C11N4TM016B — Specifications
ParameterValue
[Ir] long-time protection pick-up adjustment range0.7...1 x In
Trip unit protection functionsLI

Product details

The C11N4TM016B is a Schneider Electric ComPacT NSXm 4-pole circuit breaker rated 16 A at 40 °C with a TM-D thermal-magnetic trip unit. It carries a 50 kA interrupting capacity at 415 V AC (performance level N), certified to EN/IEC 60947-2. This is a distribution-duty breaker for panel backplate mounting, with front-facing connections and a 12-module 9 mm pitch footprint (108 mm wide).

The 16 A continuous rating at 40 °C is the breaker's thermal current (In) — it will carry 16 A indefinitely without tripping in a 40 °C ambient. Above that, the TM-D thermal-magnetic element provides overload and short-circuit protection. The 50 kA breaking capacity at 415 V AC means this breaker can safely interrupt a fault current up to 50,000 A without welding or exploding, which covers most industrial distribution panels fed by a transformer of that voltage class.

The 108 mm width (12 x 9 mm pitches) and 137 mm height fit standard panel cutouts for the NSXm family. Front-side connections accept compression lugs or busbars; neutral is on the left.

Frequently asked questions

What is the breaking capacity of C11N4TM016B?

It is rated 50 kA at 415 V AC (performance level N), certified to EN/IEC 60947-2.

What standards does C11N4TM016B comply with?

It is certified to EN/IEC 60947-2, with pollution degree 3 per IEC 60664-1 and IK07 impact resistance per IEC 62262.

Where can I buy C11N4TM016B?

This part is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time.

MPN
C11N4TM016B