In a panel with a transformer or utility feed capable of delivering 50 kA symmetrical, this breaker clears the fault without rupturing. The N performance level means it's the standard interrupting rating for the NSXm frame; if your available fault current is higher, you'd step to an H or L version. The thermal-magnetic TM-D trip unit gives you an adjustable thermal (overload) curve and a fixed magnetic (short-circuit) pickup. For a 63 A feeder, the magnetic trip typically fires at around 10x In, so 630 A instantaneous—fast enough to protect against bolted faults but coordinated with downstream 10-20 A branch breakers. The 4P (4-pole) configuration with neutral on the left handles three-phase plus neutral distribution. The neutral pole is switched and protected—important for TN-S or TT systems where you need to isolate the neutral for maintenance or where earth-leakage detection requires a switched neutral.
Schneider Electric C11N4TM063L ComPacT NSXm, 63 A, 50 kA 415
Schneider Electric ComPacT NSXm, circuit breaker, 4P, 63 A thermal-magnetic TM-D trip unit, 50 kA at 415 V AC, grey (RAL 7016).
Specifications
| Parameter | Value |
|---|---|
| Product name | ComPacT NSXm |
| Product range | ComPacT |
| Product/component type | Circuit breaker |
| Device application | Distribution |
| Parameter | Value |
|---|---|
| Rated current (In) | 63 A at 40 °C |
| Poles configuration | 4P |
| Rated operational voltage (Ue) | 690 V AC 50/60 Hz |
| Rated insulation voltage (Ui) | 800 V AC 50/60 Hz |
| Rated impulse withstand voltage (Uimp) | 8 kV |
| Network type (AC/DC) | AC |
| Network frequency | 50/60 Hz |
| Utilisation category | Category A |
| Overvoltage category | III |
| Parameter | Value |
|---|---|
| Trip unit technology | Thermal-magnetic |
| Earth-leakage protection | Without |
| Suitability for isolation | Yes conforming to IEC 60947-2 |
| Electrical durability (cycles) | 20000 cycles at 440 V In/2 10000 cycles at 440 V In 10000 cycles at 690 V In/2 5000 cycles at 690 V In |
| Mechanical durability (cycles) | 20000 cycles |
| Parameter | Value |
|---|---|
| Mounting support | Backplate |
| Control type | Toggle |
| Local signalling/indication | Flag (green) for presence of auxiliary contacts |
| Number of 9 mm pitches | 12 module |
| Parameter | Value |
|---|---|
| Operating ambient temperature | -25...70 °C |
| Storage ambient temperature | -50...85 °C |
| IP degree of protection | IP40 conforming to IEC 60529 |
| Pollution degree | 3 conforming to IEC 60664-1 |
| Relative humidity | 0...95 % |
| Parameter | Value |
|---|---|
| Standards | EN/IEC 60947-2 |
| Parameter | Value |
|---|---|
| [Icu] rated ultimate short-circuit breaking capacity | 90 kA Icu at 220...240 V AC 50/60 Hz conforming to IEC 60947-2 50 kA Icu at 380...415 V AC 50/60 Hz conforming to IEC 60947-2 50 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 25 kA Icu at 500 V AC 50/60 Hz conforming to IEC 60947-2 15 kA Icu at 525 V AC 50/60 Hz conforming to IEC 60947-2 10 kA Icu at 660...690 V AC 50/60 Hz conforming to IEC 60947-2 |
| [Ics] rated service short-circuit breaking capacity | 90 kA at 220...240 V AC 50/60 Hz conforming to IEC 60947-2 50 kA at 380...415 V AC 50/60 Hz conforming to IEC 60947-2 50 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2 25 kA at 500 V AC 50/60 Hz conforming to IEC 60947-2 15 kA at 525 V AC 50/60 Hz conforming to IEC 60947-2 2.5 kA at 660...690 V AC 50/60 Hz conforming to IEC 60947-2 |
| Parameter | Value |
|---|---|
| [Ir] long-time protection pick-up adjustment range | 0.7...1 x In |
| Trip unit protection functions | LI |
Product details
Frequently asked questions
What is the interrupting rating of C11N4TM063L?
The C11N4TM063L has a 50 kA interrupting rating at 415 V AC (N performance level). That's the maximum fault current it can safely clear at that voltage.
What standards does C11N4TM063L comply with?
It complies with EN/IEC 60947-2, the standard for low-voltage circuit breakers. It also carries suitability for isolation per that standard.
Where can I buy C11N4TM063L?
This part is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time.