Skip to main content
Schneider Electric C125H450FM — Molded Case Circuit Breakers (MCCB)

Schneider Electric C125H450FM ComPacT NS Circuit Breaker, 12

MPNC125H450FM
Active

Schneider Electric ComPacT NS new generation, C125H450FM, 4P fixed circuit breaker, 1250 A, MicroLogic 5.0 electronic trip unit, 70 kA Icu at 415 V AC, manually operated, IP40.

$6,616.00Ref. price · indicative, final on quote
Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

C125H450FM — Identification
ParameterValue
Product / component typeCircuit breaker
Device applicationDistribution
C125H450FM — Ratings
ParameterValue
Number of poles4P
C125H450FM — Electrical
ParameterValue
[In] rated current1250 A at 50 °C
Breaking capacity85 kA Icu at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 70 kA Icu at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 65 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 50 kA Icu at 500/525 V AC 50/60 Hz conforming to IEC 60947-2 42 kA Icu at 660/690 V AC 50/60 Hz conforming to IEC 60947-2
[Ics] rated service breaking capacity52 kA at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 52 kA at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 48 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2 37 kA at 500/525 V AC 50/60 Hz conforming to IEC 60947-2 31 kA at 660/690 V AC 50/60 Hz conforming to IEC 60947-2
[Ue] rated operational voltage690 V AC 50/60 Hz
[Ui] rated insulation voltage800 V AC 50/60 Hz conforming to IEC 60947-2
C125H450FM — Specifications
ParameterValue
Trip unit nameMicroLogic 5.0
Trip unit technologyElectronic
StandardsEN/IEC 60947-2

Product details

The MicroLogic 5.0 electronic trip unit provides L (long-time overload), S (short-time short-circuit), and I (instantaneous short-circuit) protection curves — no ground-fault module on this variant. Breaking capacity is 85 kA Icu at 240 V AC, 70 kA at 415 V AC, 65 kA at 440 V, 50 kA at 525 V, and 42 kA at 690 V — all at 50/60 Hz. The 20-minute thermal memory in the MicroLogic 5.0 prevents nuisance tripping on repeated inrush events, which matters for motor or transformer loads that cycle hot.

Fixed mounting on a backplate. Dimensions: 327 mm high, 280 mm wide, 147 mm deep. Connection pitch is 70 mm; both upside and downside connections are front-accessible.

Durability and signalling

Mechanical durability is 10,000 cycles. Electrical durability varies with load: 2,000 cycles at 690 V at full rated current, 3,000 at half current, 4,000 at 440 V full current, 5,000 at half current. Local signalling uses four red LEDs for fault indication and one yellow LED for overload — no remote comms on this base version.

Frequently asked questions

What is the breaking capacity of C125H450FM at 415 V?

70 kA Icu at 380/415 V AC 50/60 Hz per IEC 60947-2. The H breaking capacity code indicates this 70 kA level at 415 V.