Skip to main content
Schneider Electric C125H450FM — Miniature Circuit Breakers (MCB)

Schneider Electric C125H450FM ComPacT NS Circuit Breaker, 12

MPNC125H450FM
Active

Schneider Electric ComPacT NS new generation, C125H450FM, 4P fixed circuit breaker, 1250 A, MicroLogic 5.0 electronic trip unit, 70 kA Icu at 415 V AC, manually operated, IP40.

$6,616.00Ref. price · indicative, final on quote
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

C125H450FM — Identification
ParameterValue
Product nameComPacT NS new generation
Product rangeComPacT
Product range (series)ComPacT NS630b...1600 new generation
Product/component typeCircuit breaker
Device applicationDistribution
C125H450FM — Ratings
ParameterValue
Rated current (In)1250 A at 50 °C
Breaking capacity85 kA Icu at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 70 kA Icu at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 65 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 50 kA Icu at 500/525 V AC 50/60 Hz conforming to IEC 60947-2 42 kA Icu at 660/690 V AC 50/60 Hz conforming to IEC 60947-2
Rated service breaking capacity (Ics)52 kA at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 52 kA at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 48 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2 37 kA at 500/525 V AC 50/60 Hz conforming to IEC 60947-2 31 kA at 660/690 V AC 50/60 Hz conforming to IEC 60947-2
Rated operational voltage (Ue)690 V AC 50/60 Hz
Rated insulation voltage (Ui)800 V AC 50/60 Hz conforming to IEC 60947-2
Rated impulse withstand voltage (Uimp)8 kV conforming to IEC 60947-2
Network type (AC/DC)AC
Network frequency50/60 Hz
Utilisation categoryCategory B
Overvoltage categoryIII
C125H450FM — Protection
ParameterValue
Trip unit technologyElectronic
Earth-leakage protectionWithout
Suitability for isolationYes conforming to EN/IEC 60947-2
Electrical durability (cycles)2000 cycles at 690 V In 3000 cycles at 690 V In/2 4000 cycles at 440 V In 5000 cycles at 440 V In/2
Mechanical durability (cycles)10000 cycles
C125H450FM — Mechanical
ParameterValue
Mounting supportBackplate
Mounting modeFixed
Control typeManually operated
Local signalling/indication4 LEDs (red) for fault indication 1 LED (yellow) for overload
C125H450FM — Environmental
ParameterValue
Operating ambient temperature-25...70 °C
Storage ambient temperature-50...85 °C
IP degree of protectionIP40 conforming to IEC 60529
Pollution degree3 conforming to IEC 60947
Relative humidity0...95 %
C125H450FM — Approvals
ParameterValue
StandardsEN/IEC 60947-2
C125H450FM — Specifications
ParameterValue
[Ir] long-time protection pick-up adjustment range0.4...1 x In
Trip unit protection functionsLSI

Product details

The MicroLogic 5.0 electronic trip unit provides L (long-time overload), S (short-time short-circuit), and I (instantaneous short-circuit) protection curves — no ground-fault module on this variant. Breaking capacity is 85 kA Icu at 240 V AC, 70 kA at 415 V AC, 65 kA at 440 V, 50 kA at 525 V, and 42 kA at 690 V — all at 50/60 Hz. The 20-minute thermal memory in the MicroLogic 5.0 prevents nuisance tripping on repeated inrush events, which matters for motor or transformer loads that cycle hot.

Fixed mounting on a backplate. Dimensions: 327 mm high, 280 mm wide, 147 mm deep. Connection pitch is 70 mm; both upside and downside connections are front-accessible.

Durability and signalling

Mechanical durability is 10,000 cycles. Electrical durability varies with load: 2,000 cycles at 690 V at full rated current, 3,000 at half current, 4,000 at 440 V full current, 5,000 at half current. Local signalling uses four red LEDs for fault indication and one yellow LED for overload — no remote comms on this base version.

Frequently asked questions

What is the breaking capacity of C125H450FM at 415 V?

70 kA Icu at 380/415 V AC 50/60 Hz per IEC 60947-2. The H breaking capacity code indicates this 70 kA level at 415 V.

Where can I buy C125H450FM and get current pricing?

This part is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time — submit an RFQ for a firm price and lead time.

What protection curves does the MicroLogic 5.0 trip unit provide?

The MicroLogic 5.0 electronic trip unit provides L (long-time overload), S (short-time short-circuit), and I (instantaneous short-circuit) protection. This variant does not include earth-leakage protection.

MPN