Skip to main content
Schneider Electric C125H45EFM — Molded Case Circuit Breakers (MCCB)

C125H45EFM ComPacT NS 1250A 4P MCCB, MicroLogic 5.0 E, 70 kA

MPNC125H45EFM
Active

Schneider Electric ComPacT NS new generation, C125H45EFM, 4-pole MCCB, 1250 A, MicroLogic 5.0 E trip unit, 70 kA Icu at 415 V AC, fixed mount, LCD display, energy meter.

$3,842.71Ref. price · indicative, final on quote
Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

C125H45EFM — Identification
ParameterValue
Product / component typeCircuit breaker
Device applicationDistribution
C125H45EFM — Ratings
ParameterValue
Number of poles4P
C125H45EFM — Electrical
ParameterValue
[In] rated current1250 A at 50 °C
Breaking capacity85 kA Icu at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 70 kA Icu at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 65 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 50 kA Icu at 500/525 V AC 50/60 Hz conforming to IEC 60947-2 42 kA Icu at 660/690 V AC 50/60 Hz conforming to IEC 60947-2
[Ics] rated service breaking capacity52 kA at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 52 kA at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 48 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2 37 kA at 500/525 V AC 50/60 Hz conforming to IEC 60947-2 31 kA at 660/690 V AC 50/60 Hz conforming to IEC 60947-2
[Ue] rated operational voltage690 V AC 50/60 Hz
[Ui] rated insulation voltage800 V AC 50/60 Hz conforming to IEC 60947-2
C125H45EFM — Specifications
ParameterValue
Trip unit nameMicroLogic 5.0 E
Trip unit technologyElectronic
StandardsEN/IEC 60947-2

Product details

Schneider Electric C125H45EFM is a 4-pole fixed-mount ComPacT NS new generation MCCB. Rated 1250 A at 50 °C with a MicroLogic 5.0 E electronic trip unit that includes an integrated energy meter — the E suffix means it measures and reports energy consumption directly through the trip unit's LCD display. Breaking capacity is 70 kA Icu at 380/415 V AC 50/60 Hz per IEC 60947-2, with a code H designation. At 220/240 V it reaches 85 kA Icu, and at 660/690 V it holds 42 kA Icu. The trip unit provides L (long-time overload), S (short-time short-circuit), and I (instantaneous) protection curves, plus a 20-minute thermal memory. That thermal memory prevents nuisance tripping on reclose after a brief overload — the breaker remembers the previous thermal state and adjusts the curve so it doesn't trip too early on a second start.

Fixed backplate mount, 327 mm high × 280 mm wide × 147 mm deep. Front connections both top and bottom — wire entry and busbar landing on the same face, which simplifies panel layout. Connection pitch is 70 mm, standard for this frame size. IP40 enclosure protection, IK07 impact resistance. Manually operated with an LCD display showing measured values and fault codes — four red LEDs for fault indication, one yellow for overload. Neutral on the left. Rated for 0–2000 m altitude without derating; above that up to 5000 m with derating. 0–95 % relative humidity range.

Frequently asked questions

What breaking capacity does C125H45EFM have at 415 V?

70 kA Icu at 380/415 V AC 50/60 Hz per IEC 60947-2. The H breaking capacity code designates this level. At 220/240 V it reaches 85 kA Icu, and at 660/690 V it holds 42 kA Icu.

What trip unit does C125H45EFM use?

MicroLogic 5.0 E electronic trip unit with L (overload), S (short-time short-circuit), and I (instantaneous) protection. The E suffix adds integrated energy metering displayed on the LCD. Trip rating is 1250 A at 50 °C.

What compliance standards does C125H45EFM meet?

Designed and tested to EN/IEC 60947-2. Rated for pollution degree 3 and overvoltage category III. IP40 enclosure, IK07 impact resistance. Altitude rating 0–2000 m without derating, up to 5000 m with derating.

MPN
C125H45EFM