Skip to main content
Schneider Electric C125N32AFM — Miniature Circuit Breakers (MCB)

Schneider C125N32AFM ComPacT NS new generation MCCB, 1250 A, 3-pole

MPNC125N32AFM
Active

Schneider C125N32AFM Compact Ns New Generation — now discontinued, supplied from remaining surplus and broker stock.

$3,965.47Ref. price · indicative, final on quote
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jun 2026

Specifications

C125N32AFM — Identification
ParameterValue
Product nameComPacT NS new generation
Product rangeComPacT
Product range (series)ComPacT NS630b...1600 new generation
Product/component typeCircuit breaker
Device applicationDistribution
C125N32AFM — Ratings
ParameterValue
Rated current (In)1250 A at 50 °C
Breaking capacity85 kA Icu at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 50 kA Icu at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 50 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 40 kA Icu at 500/525 V AC 50/60 Hz conforming to IEC 60947-2 30 kA Icu at 660/690 V AC 50/60 Hz conforming to IEC 60947-2
Rated service breaking capacity (Ics)50 kA at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 50 kA at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 50 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2 40 kA at 500/525 V AC 50/60 Hz conforming to IEC 60947-2 30 kA at 660/690 V AC 50/60 Hz conforming to IEC 60947-2
Rated operational voltage (Ue)690 V AC 50/60 Hz
Rated insulation voltage (Ui)800 V AC 50/60 Hz conforming to IEC 60947-2
Rated impulse withstand voltage (Uimp)8 kV conforming to IEC 60947-2
Network type (AC/DC)AC
Network frequency50/60 Hz
Utilisation categoryCategory B
Overvoltage categoryIII
C125N32AFM — Protection
ParameterValue
Trip unit technologyElectronic
Earth-leakage protectionWithout
Suitability for isolationYes conforming to EN/IEC 60947-2
Electrical durability (cycles)2000 cycles at 690 V In 3000 cycles at 690 V In/2 4000 cycles at 440 V In 5000 cycles at 440 V In/2
Mechanical durability (cycles)10000 cycles
C125N32AFM — Mechanical
ParameterValue
Mounting supportBackplate
Mounting modeFixed
Control typeManually operated
Local signalling/indication4 LEDs (red) for fault indication 1 LED (yellow) for overload
C125N32AFM — Environmental
ParameterValue
Operating ambient temperature-25...70 °C
Storage ambient temperature-40...85 °C
IP degree of protectionIP40 conforming to IEC 60529
Pollution degree3 conforming to IEC 60947
Relative humidity0...95 %
C125N32AFM — Approvals
ParameterValue
StandardsEN/IEC 60947-2
C125N32AFM — Specifications
ParameterValue
[Ir] long-time protection pick-up adjustment range0.4...1 x In
Trip unit protection functionsLI

Product details

Overview

The C125N32AFM is a Schneider ComPacT NS new generation 3-pole molded case circuit breaker rated 1250 A with a MicroLogic 2.0 A electronic trip unit providing L (long-time overload) and I (instantaneous short-circuit) protection. It breaks 85 kA at 690 V AC and meets EN/IEC 60947-2.

The C125N32AFM carries 3 poles; the C125N42AFM carries 4 poles with neutral protection settings (No protection (3D), 0.5 x Ir (3D + N/2), 1 x Ir (4D)). The C125N42AFM also adds short-time protection (S) and adjustable Isd and Tsd. If your panel is wired for 4-wire distribution, the C125N42AFM is the correct choice; the C125N32AFM fits 3-pole-only feeds.

MPN
C125N32AFM