Skip to main content
Schneider Electric C125N32EFM — Miniature Circuit Breakers (MCB)

C125N32EFM ComPacT NS new generation, 1250 A, 50 kA at 415 V

MPNC125N32EFM
Active

Schneider Electric ComPacT NS new generation, C125N32EFM, 3P fixed-mount MCCB, 1250 A MicroLogic 2.0 E electronic trip unit, 50 kA Icu at 415 V AC, IP40, current lifecycle.

$2,562.16Ref. price · indicative, final on quote
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

C125N32EFM — Identification
ParameterValue
Product nameComPacT NS new generation
Product rangeComPacT
Product range (series)ComPacT NS630b...1600 new generation
Product/component typeCircuit breaker
Device applicationDistribution
C125N32EFM — Ratings
ParameterValue
Rated current (In)1250 A at 50 °C
Breaking capacity85 kA Icu at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 50 kA Icu at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 50 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 40 kA Icu at 500/525 V AC 50/60 Hz conforming to IEC 60947-2 30 kA Icu at 660/690 V AC 50/60 Hz conforming to IEC 60947-2
Rated service breaking capacity (Ics)50 kA at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 50 kA at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 50 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2 40 kA at 500/525 V AC 50/60 Hz conforming to IEC 60947-2 30 kA at 660/690 V AC 50/60 Hz conforming to IEC 60947-2
Rated operational voltage (Ue)690 V AC 50/60 Hz
Rated insulation voltage (Ui)800 V AC 50/60 Hz conforming to IEC 60947-2
Rated impulse withstand voltage (Uimp)8 kV conforming to IEC 60947-2
Network type (AC/DC)AC
Network frequency50/60 Hz
Utilisation categoryCategory B
Overvoltage categoryIII
C125N32EFM — Protection
ParameterValue
Trip unit technologyElectronic
Earth-leakage protectionWithout
Suitability for isolationYes conforming to EN/IEC 60947-2
Electrical durability (cycles)2000 cycles at 690 V In 3000 cycles at 690 V In/2 4000 cycles at 440 V In 5000 cycles at 440 V In/2
Mechanical durability (cycles)10000 cycles
C125N32EFM — Mechanical
ParameterValue
Mounting supportBackplate
Mounting modeFixed
Control typeManually operated
Local signalling/indication4 LEDs (red) for fault indication 1 LED (yellow) for overload
C125N32EFM — Environmental
ParameterValue
Operating ambient temperature-25...70 °C
Storage ambient temperature-40...85 °C
IP degree of protectionIP40 conforming to IEC 60529
Pollution degree3 conforming to IEC 60947
Relative humidity0...95 %
C125N32EFM — Approvals
ParameterValue
StandardsEN/IEC 60947-2
C125N32EFM — Specifications
ParameterValue
[Ir] long-time protection pick-up adjustment range0.4...1 x In
Trip unit protection functionsLI

Product details

The C125N32EFM is a 3-pole fixed-mount ComPacT NS new generation MCCB from Schneider Electric, rated 1250 A at 50 °C with a MicroLogic 2.0 E electronic trip unit. It carries an N breaking capacity code — 50 kA Icu at 380/415 V AC per IEC 60947-2 — which means it can safely interrupt a bolted fault up to that level on a 415 V distribution bus without upstream cascading.

The MicroLogic 2.0 E provides L (long-time overload) and I (instantaneous short-circuit) protection curves, with an electronic trip unit that holds thermal memory for 20 minutes after a trip event. That thermal memory matters for motor or transformer feeders where repeated inrush can heat the conductor without reaching the instantaneous threshold — the trip unit remembers the prior thermal state and shortens the allowable cool-down. The energy meter measurement type means the unit reports energy consumption data through the LCD display, useful for submetering a distribution panel without a separate meter.

Rated Icu at 440 V AC is 50 kA, dropping to 40 kA at 500/525 V AC and 30 kA at 660/690 V AC. The utilisation category B rating means the breaker is tested for selectivity under short-circuit conditions — it can be used as the main or tie breaker in a selective scheme where downstream devices clear faster and this unit stays closed to keep healthy feeders live.

Physical integration and environment

Fixed backplate mount, 210 mm wide by 327 mm tall by 147 mm deep, with a 70 mm connection pitch. IP40 enclosure protection keeps out tools and debris but is not rated for washdown — this is a dry indoor gear installation. IK07 impact rating means it withstands a 2 J hammer blow, typical for a switchboard environment.

Operating altitude is 0 to 2000 m without derating, with derating required above 2000 m up to 5000 m.

Frequently asked questions

Where can I buy C125N32EFM and how is it quoted?

We source C125N32EFM to order against an RFQ through independent distribution channels. Availability and current pricing are confirmed at quote time — submit an RFQ for a firm price and lead time.

What is the breaking capacity of C125N32EFM at 415 V?

50 kA Icu at 380/415 V AC per IEC 60947-2, with an N breaking capacity code. At 220/240 V AC it is 85 kA Icu.

What trip unit does C125N32EFM use?

A MicroLogic 2.0 E electronic trip unit providing L (long-time overload) and I (instantaneous short-circuit) protection, with a 20-minute thermal memory and an energy meter measurement function.

What are the physical dimensions of C125N32EFM?

210 mm wide, 327 mm tall, 147 mm deep. Fixed backplate mount with front-facing connections and a 70 mm connection pitch.

MPN