Skip to main content
Schneider Electric C125N32EFM — Molded Case Circuit Breakers (MCCB)

C125N32EFM ComPacT NS new generation, 1250 A, 50 kA at 415 V

MPNC125N32EFM
Active

Schneider Electric ComPacT NS new generation, C125N32EFM, 3P fixed-mount MCCB, 1250 A MicroLogic 2.0 E electronic trip unit, 50 kA Icu at 415 V AC, IP40, current lifecycle.

$2,562.16Ref. price · indicative, final on quote
Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

C125N32EFM — Identification
ParameterValue
Product / component typeCircuit breaker
Device applicationDistribution
C125N32EFM — Ratings
ParameterValue
Number of poles3P
C125N32EFM — Electrical
ParameterValue
[In] rated current1250 A at 50 °C
Breaking capacity85 kA Icu at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 50 kA Icu at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 50 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 40 kA Icu at 500/525 V AC 50/60 Hz conforming to IEC 60947-2 30 kA Icu at 660/690 V AC 50/60 Hz conforming to IEC 60947-2
[Ics] rated service breaking capacity50 kA at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 50 kA at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 50 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2 40 kA at 500/525 V AC 50/60 Hz conforming to IEC 60947-2 30 kA at 660/690 V AC 50/60 Hz conforming to IEC 60947-2
[Ue] rated operational voltage690 V AC 50/60 Hz
[Ui] rated insulation voltage800 V AC 50/60 Hz conforming to IEC 60947-2
C125N32EFM — Specifications
ParameterValue
Trip unit nameMicroLogic 2.0 E
Trip unit technologyElectronic
StandardsEN/IEC 60947-2

Product details

The C125N32EFM is a 3-pole fixed-mount ComPacT NS new generation MCCB from Schneider Electric, rated 1250 A at 50 °C with a MicroLogic 2.0 E electronic trip unit. It carries an N breaking capacity code — 50 kA Icu at 380/415 V AC per IEC 60947-2 — which means it can safely interrupt a bolted fault up to that level on a 415 V distribution bus without upstream cascading.

The MicroLogic 2.0 E provides L (long-time overload) and I (instantaneous short-circuit) protection curves, with an electronic trip unit that holds thermal memory for 20 minutes after a trip event. That thermal memory matters for motor or transformer feeders where repeated inrush can heat the conductor without reaching the instantaneous threshold — the trip unit remembers the prior thermal state and shortens the allowable cool-down. The energy meter measurement type means the unit reports energy consumption data through the LCD display, useful for submetering a distribution panel without a separate meter.

Rated Icu at 440 V AC is 50 kA, dropping to 40 kA at 500/525 V AC and 30 kA at 660/690 V AC. The utilisation category B rating means the breaker is tested for selectivity under short-circuit conditions — it can be used as the main or tie breaker in a selective scheme where downstream devices clear faster and this unit stays closed to keep healthy feeders live.

Physical integration and environment

Fixed backplate mount, 210 mm wide by 327 mm tall by 147 mm deep, with a 70 mm connection pitch. IP40 enclosure protection keeps out tools and debris but is not rated for washdown — this is a dry indoor gear installation. IK07 impact rating means it withstands a 2 J hammer blow, typical for a switchboard environment.

Operating altitude is 0 to 2000 m without derating, with derating required above 2000 m up to 5000 m.

Frequently asked questions

Where can I buy C125N32EFM and how is it quoted?

We source C125N32EFM to order against an RFQ through independent distribution channels. Availability and current pricing are confirmed at quote time — submit an RFQ for a firm price and lead time.

What is the breaking capacity of C125N32EFM at 415 V?

50 kA Icu at 380/415 V AC per IEC 60947-2, with an N breaking capacity code. At 220/240 V AC it is 85 kA Icu.

What trip unit does C125N32EFM use?

A MicroLogic 2.0 E electronic trip unit providing L (long-time overload) and I (instantaneous short-circuit) protection, with a 20-minute thermal memory and an energy meter measurement function.

What are the physical dimensions of C125N32EFM?

210 mm wide, 327 mm tall, 147 mm deep. Fixed backplate mount with front-facing connections and a 70 mm connection pitch.