Schneider Electric C125S3WM — Molded Case Circuit Breakers (MCCB)

C125S3WM ComPacT NS Switch Disconnector, 1250A, 3P, Drawout

MPNC125S3WM
Active

Schneider Electric ComPacT NS new generation, switch disconnector basic frame C125S3WM, 3P, drawout, manually operated, 1250 A AC-23A, 690 V AC, IEC 60947-3.

$1,237.28Ref. price · indicative, final on quote
Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

C125S3WM — Identification
ParameterValue
Product / component typeBasic frame
Device applicationDistribution
C125S3WM — Mechanical
ParameterValue
Height210 mm
Width327 mm
Depth147 mm
C125S3WM — Specifications
ParameterValue
Poles description3P
StandardsIEC 60947-3
C125S3WM — Electrical
ParameterValue
[Ue] rated operational voltage690 V AC 50/60 Hz conforming to IEC 60947-3
[Ui] rated insulation voltage800 V AC 50/60 Hz conforming to IEC 60947-3

Product details

Switch disconnector for distribution, 1250 A drawout frame

The C125S3WM is a Schneider Electric ComPacT NS new generation switch disconnector basic frame, 3-pole, drawout, manually operated, rated 1250 A in AC-23A duty across 220–690 V AC. That AC-23A rating covers switching of motor loads and other highly inductive loads — not just resistive — so it handles the inrush and make-break duty of downstream contactors and motor starters. The drawout (withdrawable) mounting means the moving portion can be racked out for safe maintenance without disturbing the fixed cradle connections — standard practice in switchgear where isolation and padlock-out are required.

Rated operational current (Ie) is 1250 A in AC-23A at all standard voltages from 220 V to 690 V AC — no derating curve to chase across the voltage band. Conventional free-air thermal current (Ith) is 1250 A at 60 °C, so the frame is sized for continuous full-load current in a typical enclosed switchboard. Short-time withstand (Icw) is 25 kA for 0.5 s, and short-circuit making capacity (Icm) is 52 kA at 690 V. These numbers govern selectivity coordination with upstream breakers: the 25 kA / 0.5 s withstand lets downstream protection clear a fault without the disconnector failing closed. Mechanical durability is 10,000 cycles; electrical durability is 2,000 cycles at 440 V. For a manually operated distribution disconnector that sees infrequent switching (isolation, not daily motor starting), that cycle life is ample — not a wear-item concern in normal service. IP40 enclosure protection keeps out tools and small solids; IK07 impact rating means it withstands a 0.5 J hammer blow — typical for indoor switchgear cubicles.

Frequently asked questions

What is the rated operational current of C125S3WM?

Rated operational current (Ie) is 1250 A in AC-23A duty across 220–690 V AC. Conventional free-air thermal current (Ith) is also 1250 A at 60 °C.

What standard does C125S3WM comply with?

The C125S3WM is designed and tested to IEC 60947-3, the standard for switches, disconnectors, switch-disconnectors and fuse-combination units. Pollution degree 3, rated insulation voltage 800 V, impulse withstand 8 kV — all per that standard.