Schneider Electric C12E6TM160B — Miniature Circuit Breakers (MCB)

Schneider Electric C12E6TM160B ComPacT NSXm Circuit Breaker,

MPNC12E6TM160B
Active

Schneider Electric ComPacT NSXm, C12E6TM160B, 4P MCCB, 160 A at 40 °C, TM-D thermal-magnetic trip, 16 kA 415 V AC, EN/IEC 60947-2.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

C12E6TM160B — Identification
ParameterValue
Product nameComPacT NSXm
Product rangeComPacT
Product/component typeCircuit breaker
Device applicationDistribution
C12E6TM160B — Ratings
ParameterValue
Rated current (In)160 A at 40 °C
Poles configuration4P
Rated operational voltage (Ue)440 V AC 50/60 Hz
Rated insulation voltage (Ui)800 V AC 50/60 Hz
Rated impulse withstand voltage (Uimp)8 kV
Network type (AC/DC)AC
Network frequency50/60 Hz
Utilisation categoryCategory A
Overvoltage categoryIII
C12E6TM160B — Protection
ParameterValue
Trip unit technologyThermal-magnetic
Earth-leakage protectionWithout
Suitability for isolationYes conforming to IEC 60947-2
Electrical durability (cycles)20000 cycles at 440 V In/2 10000 cycles at 440 V In
Mechanical durability (cycles)20000 cycles
C12E6TM160B — Mechanical
ParameterValue
Mounting supportBackplate
Control typeToggle
Local signalling/indicationFlag (green) for presence of auxiliary contacts
Number of 9 mm pitches12 module
C12E6TM160B — Environmental
ParameterValue
Operating ambient temperature-25...70 °C
Storage ambient temperature-50...85 °C
IP degree of protectionIP40 conforming to IEC 60529
Pollution degree3 conforming to IEC 60664-1
Relative humidity0...95 %
C12E6TM160B — Approvals
ParameterValue
StandardsEN/IEC 60947-2
C12E6TM160B — Electrical
ParameterValue
[Icu] rated ultimate short-circuit breaking capacity25 kA Icu at 220...240 V AC 50/60 Hz conforming to IEC 60947-2 16 kA Icu at 380...415 V AC 50/60 Hz conforming to IEC 60947-2 10 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2
[Ics] rated service short-circuit breaking capacity25 kA at 220...240 V AC 50/60 Hz conforming to IEC 60947-2 16 kA at 380...415 V AC 50/60 Hz conforming to IEC 60947-2 10 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2
C12E6TM160B — Specifications
ParameterValue
[Ir] long-time protection pick-up adjustment range0.7...1 x In
Trip unit protection functionsLI

Product details

Rated for isolation per IEC 60947-2, so it doubles as a visible-break disconnect when the toggle is off — no separate switch needed upstream for routine isolation.

The 160 A frame (NSXm 160E) is the smallest in the ComPacT NSXm range, sized for 12 module pitches at 9 mm each (108 mm wide) — it fits standard backplate mounting in enclosures where panel width is tight. The TM-D trip unit is thermal-magnetic, category A (no intentional short-time delay), so it coordinates downstream with standard MCBs but not with time-delayed breakers upstream. Front connection terminals accept compression lugs or busbars; the neutral is fixed on the left, and the breaker mounts horizontally or vertically flat on the backplate. IP40 front face and IK07 impact resistance handle accidental tool contact in a closed panel — not rated for washdown, but fine for indoor switchgear.

Frequently asked questions

How do I get current pricing and availability for C12E6TM160B?

Submit an RFQ through this listing. Availability and current pricing are confirmed at quote time; the part is sourced to order through independent distribution.

What is C12E6TM160B's listed range (ComPacT) on this component line?

The range is ComPacT, and the product name is ComPacT NSXm — the smallest frame in Schneider's moulded-case breaker family for distribution applications.

What compliance documentation does this brand provide for C12E6TM160B?

The breaker is certified to EN/IEC 60947-2. RoHS and REACH declarations are available from the manufacturer on request.

MPN
C12E6TM160B