Skip to main content
Schneider Electric C163160S

Schneider Electric C163160S

MPNC163160S
Active

Switch disconnector, ComPacT NSX160NA, 3 poles, fixed, thermal current Ith 160A

$200.14 – $223.13Ref. price · indicative, final on quote
Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

C163160S key specifications
ParameterValue
Control typeToggle
Network typeDC AC
Product or component typeSwitch disconnector
Voltage800 V AC 50/60 Hz
[Ue] rated operational voltage690 V AC 50/60 Hz 750 V DC 3 poles in series 500 V DC 2 poles in series 250 V DC 1 pole
[Uimp] rated impulse withstand voltage8 kV
[Icw] rated short-time withstand current2.5 kA during 1 s 2.5 kA during 3 s 0.96 kA during 20 s
[Ie] rated operational currentAC-22A: 160 A AC 50/60 Hz 220...690 V AC-23A: 160 A AC 50/60 Hz 220...690 V DC-22A: 160 A DC 250 V 1 pole DC-22A: 160 A DC 500 V 2 poles in series DC-23A: 160 A DC 250 V 1 pole DC-23A: 160 A DC 500 V 2 poles in series DC-22A: 160 A DC 750 V 3 poles in series DC-23A: 160 A DC 750 V 3 poles in series
[Icm] rated short-circuit making capacity330 kA with upstream protection circuit breaker 3.6 kA switch-disconnector alone
[Ith] conventional free air thermal current160 A at 50 °C
Poles description3P
Utilisation categoryAC-22A AC-23A DC-22A DC-23A

All specifications

C163160S additional specifications
ParameterValue
IK degree of protectionIK07 conforming to IEC 62262
IP degree of protectionIP40 conforming to IEC 60529
Mounting modeFixed
Mounting supportBackplate
Connection pitch35 mm
Upside connectionFront
Downside connectionFront
Pollution degree3 conforming to IEC 60664-1
Electrical shock protection classClass II
Depth86 mm
Width105 mm
Height161 mm
Electrical durabilityAC-22A: 30000 cycles 440 V AC 50/60 Hz In/2 AC-23A: 30000 cycles 440 V AC 50/60 Hz In/2 AC-22A: 15000 cycles 440 V AC 50/60 Hz In AC-23A: 15000 cycles 440 V AC 50/60 Hz In AC-22A: 10000 cycles 690 V AC 50/60 Hz In/2 AC-23A: 10000 cycles 690 V AC 50/60 Hz In/2 AC-22A: 5000 cycles 690 V AC 50/60 Hz In AC-23A: 5000 cycles 690 V AC 50/60 Hz In DC-22A: 10000 cycles 250 V DC In/2 (1 pole) DC-23A: 10000 cycles 250 V DC In/2 (1 pole) DC-22A: 5000 cycles 500 V DC In (2 poles in series) DC-23A: 5000 cycles 500 V DC In (2 poles in series)
Mechanical durability40000 cycles
StandardsEN/IEC 60947-1 EN/IEC 60947-3
RangeComPacT
Visible breakNo
Device short nameNSX160NA
Device applicationDistribution
Suitability for isolationYes conforming to EN/IEC 60947-3
Contact position indicatorYes
Ambient air temperature for storage-50...85 °C
Ambient air temperature for operation-25...70 °C
MPN
C163160S