Skip to main content
Schneider Electric C1632M150

Schneider Electric C1632M150

MPNC1632M150
Active

Trip unit MicroLogic 2.2 M for ComPacT NSX 160/250 circuit breakers, electronic, rating 150A, 3 poles 3d

$242.73 – $348.42Ref. price · indicative, final on quote
StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026
How we verify every order →

Specifications

C1632M150 key specifications
ParameterValue
Network typeAC
Protection typeL : for overload protection (long time) So : for short time short-circuit protection with fixed delay I : for instantaneous short-circuit protection
Range of productComPacT NSX100...250
Product or component typeTrip unit
Long-time protection delay adjustment type trFixed
Short-time protection delay adjustment type tsdFixed
Short-time protection pick-up adjustment type isdAdjustable 9 settings
Instantaneous protection pick-up adjustment type iiFixed
Long-time pick-up adjustment type ir (thermal protection)Adjustable 9 settings
[Ue] rated operational voltage690 V AC 50/60 Hz
Network frequency50/60 Hz
Poles description3P

All specifications

C1632M150 additional specifications
ParameterValue
Protected poles description3D
IP degree of protectionIP40 conforming to IEC 60529
Circuit breaker mounting modeFixed
Pollution degree3 conforming to IEC 60947-1
Electrical shock protection classClass II
StandardsEN/IEC 60947-2
RangeComPacT
Thermal memory20 minutes before and after tripping
Trip unit nameMicroLogic 2.2 M
Local signallingFlashing LED (green) for ready to operate LED 95 % Ith (red) for temperature over set point
Trip unit rating150 A at 65 °C
Device applicationMotor
Motor tripping class10 5 20
Trip unit technologyElectronic
Earth-leakage protectionWithout
Complementary motor protectionPhase unbalance
Trip unit protection functionsLSoI
Zone selective interlocking ZSIWithout
Ambient air temperature for storage-50...85 °C
Ambient air temperature for operation-25...70 °C
[Tr] Long-Time protection delay adjustment range120 s at 1.5 x Ir for trip class 5 6.5 s at 6 x Ir for trip class 5 5 s at 7.2 x Ir for trip class 5 240 s at 1.5 x Ir for trip class 10 13.5 s at 6 x Ir for trip class 10 10 s at 7.2 x Ir for trip class 10 480 s at 1.5 x Ir for trip class 20 26 s at 6 x Ir for trip class 20 20 s at 7.2 x Ir for trip class 20
[Ir] long-time protection pick-up adjustment range70...150 A
[Isd] short-time protection pick-up adjustment range5...13 x Ir
[Ii] instantaneous protection pick-up adjustment range2250 A
MPN