Schneider Electric C163TM125
MPNC163TM125
Active
TRIP UNIT NSX160 AC 3P3D 125A TMD|TRIP UNIT NSX160 AC 3P3D 125A TMD
$130.81Ref. price · indicative, final on quote
StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026
How we verify every order →Specifications
| Parameter | Value |
|---|---|
| Network type | AC |
| Protection type | L : for overload protection (thermal) I : for short-circuit protection (magnetic) |
| Range of product | ComPacT NSX100...250 |
| Product or component type | Trip unit |
| Long-time protection delay adjustment type tr | Fixed |
| Instantaneous protection pick-up adjustment type ii | Fixed |
| Long-time pick-up adjustment type ir (thermal protection) | Adjustable |
| [Ue] rated operational voltage | 690 V AC 50/60 Hz |
| Network frequency | 50/60 Hz |
| Poles description | 3P |
| Protected poles description | 3D |
| IP degree of protection | IP40 conforming to IEC 60529 |
All specifications
| Parameter | Value |
|---|---|
| Circuit breaker mounting mode | Fixed |
| Pollution degree | 3 conforming to IEC 60947-1 |
| Electrical shock protection class | Class II |
| Standards | EN/IEC 60947-2 |
| Range | ComPacT |
| Trip unit name | TM-D |
| Trip unit rating | 125 A at 40 °C |
| Device application | Distribution |
| Trip unit technology | Thermal-magnetic |
| Earth-leakage protection | Without |
| Trip unit protection functions | LI |
| Ambient air temperature for storage | -50...85 °C |
| Ambient air temperature for operation | -25...70 °C |
| [Tr] Long-Time protection delay adjustment range | 120...400 s at 1.5 x In 15 s at 6 x Ir |
| [Ir] long-time protection pick-up adjustment range | 0.7...1 x In |
| [Ii] instantaneous protection pick-up adjustment range | 1250 A |
MPN
C163TM125