Specifications

C16B34V160 key specifications
ParameterValue
Control typeToggle
Network typeAC
Protection typeL : for overload protection (long time) So : for short time short-circuit protection with fixed delay I : for instantaneous short-circuit protection R : for earth-leakage protection
Product or component typeEarth leakage circuit breaker
Long-time protection delay adjustment type trFixed
Short-time protection delay adjustment type tsdFixed
Short-time protection pick-up adjustment type isdAdjustable
Instantaneous protection pick-up adjustment type iiFixed
Earth-leakage protection sensitity adjustment type iδnAdjustable
Earth-leakage protection time delay adjustement type δtAdjustable
Long-time pick-up adjustment type ir (thermal protection)Adjustable 9 settings
Voltage500 V AC 50/60 Hz

All specifications

C16B34V160 additional specifications
ParameterValue
[Ue] rated operational voltage440 V AC 50/60 Hz
[Uimp] rated impulse withstand voltage8 kV
Breaking capacity40 kA Icu at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 25 kA Icu at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 20 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 15 kA Icu at 500 V AC 50/60 Hz conforming to IEC 60947-2
Current160 A at 40 °C
Breaking capacity codeB 25 kA 415 V AC
[Ics] rated service breaking capacity40 kA at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 25 kA at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 20 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2 15 kA at 500 V AC 50/60 Hz conforming to IEC 60947-2
Power dissipation per pole12.3 W N 12.3 W L1 and L3 10 W L2
Network frequency50/60 Hz
Poles description3P
Protected poles description3D
Utilisation categoryCategory A
IK degree of protectionIK07 conforming to IEC 62262
IP degree of protectionIP40 conforming to IEC 60529
Mounting supportBackplate
Mounting positionHorizontal and vertical Flat on the back
Circuit breaker mounting modeFixed
Connection pitch35 mm
Upside connectionFront
Downside connectionFront
Pollution degree3 conforming to IEC 60664-1
Relative humidity0...95 %
Operating altitude0...2000 m without derating 2000 m...5000 m with derating
Electrical shock protection classClass II on front face
Depth86 mm
Width105 mm
Height161 mm
Electrical durability40000 cycles at 440 V In/2 20000 cycles at 440 V In 15000 cycles at 690 V In/2 7500 cycles at 690 V In
Mechanical durability40000 cycles
StandardsEN/IEC 60947-2
RangeComPacT
Operating modeOFF using the IΔn rotary switch
Thermal memory20 minutes before and after tripping
Trip unit nameMicroLogic 4.2
Number of slots5 slot(s)
Local signallingFlashing LED (green) for ready to operate LED 105 % Ir (red) for overload LED 90 % Ir (orange) for overload
Trip unit rating160 A at 40 °C
Device short nameNSX160B
Device applicationDistribution
Overvoltage categoryIV
Trip unit technologyElectronic
Earth-leakage protectionIntegrated
Suitability for isolationYes conforming to EN/IEC 60947-2
Earth-leakage protection classClass A
Trip unit protection functionsLSoIR
Zone selective interlocking ZSIWithout
Ambient air temperature for storage-50...85 °C
Ambient air temperature for operation-25...70 °C
[Tr] Long-Time delay adjustment range400 s at 1.5 x Ir 16 s at 6 x Ir 11 s at 7.2 x Ir
[Ir] long-time protection pick-up adjustment range63...160 A
[δt] residual earth-leakage time delay adjustment0 ms 60 ms 150 ms 500 ms 1 s
[Isd] short-time protection pick-up adjustment range1.5...10 x Ir
[Ii] instantaneous protection pick-up adjustment range2400 A
[IΔn] earth-leakage protection sensitivity adjustment range30 mA 100 mA 300 mA 500 mA 1 A 3 A 5 A
MPN