Skip to main content
Schneider Electric C16F4TM160

Schneider Electric C16F4TM160

MPNC16F4TM160
Active

C16F4TM160 - NSX160F 36KA AC 4P4D 160A TMD by SCHNEIDER ELECTRIC

$533.40Ref. price · indicative, final on quote
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

C16F4TM160 key specifications
ParameterValue
Control typeToggle
Network typeAC
Protection typeL : for overload protection (thermal) I : for short-circuit protection (magnetic)
Product or component typeCircuit breaker
Long-time protection delay adjustment type trFixed
Instantaneous protection pick-up adjustment type iiFixed
Long-time pick-up adjustment type ir (thermal protection)Adjustable
Voltage800 V AC 50/60 Hz
[Ue] rated operational voltage690 V AC 50/60 Hz
[Uimp] rated impulse withstand voltage8 kV
Breaking capacity85 kA Icu at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 36 kA Icu at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 35 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 30 kA Icu at 500 V AC 50/60 Hz conforming to IEC 60947-2 22 kA Icu at 525 V AC 50/60 Hz conforming to IEC 60947-2 8 kA Icu at 660/690 V AC 50/60 Hz conforming to IEC 60947-2 85 kA Icu at 240 V AC 50/60 Hz conforming to UL 60947-4-1 35 kA Icu at 480 V AC 50/60 Hz conforming to UL 60947-4-1 10 kA Icu at 600 V AC 50/60 Hz conforming to UL 60947-4-1
Current160 A at 40 °C

All specifications

C16F4TM160 additional specifications
ParameterValue
Breaking capacity codeF 36 kA 415 V AC
[Ics] rated service breaking capacity85 kA at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 36 kA at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 35 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2 30 kA at 500 V AC 50/60 Hz conforming to IEC 60947-2 22 kA at 525 V AC 50/60 Hz conforming to IEC 60947-2 8 kA at 660/690 V AC 50/60 Hz conforming to IEC 60947-2
Power dissipation per pole13.95 W
Network frequency50/60 Hz
Poles description4P
Protected poles description4D
Utilisation categoryCategory A
IK degree of protectionIK07 conforming to IEC 62262
IP degree of protectionIP40 conforming to IEC 60529
Mounting supportBackplate
Mounting positionHorizontal and vertical Flat on the back
Circuit breaker mounting modeFixed
Connection pitch35 mm
Upside connectionFront
Downside connectionFront
Pollution degree3 conforming to IEC 60664-1
Relative humidity0...95 %
Operating altitude0...2000 m without derating 2000 m...5000 m with derating
Electrical shock protection classClass II on front face
Depth86 mm
Width140 mm
Height161 mm
Electrical durability40000 cycles at 440 V In/2 20000 cycles at 440 V In 15000 cycles at 690 V In/2 7500 cycles at 690 V In
Mechanical durability40000 cycles
StandardsEN/IEC 60947-2
RangeComPacT
Trip unit nameTM-D
Number of slots5 slot(s)
Neutral positionLeft
Trip unit rating160 A at 40 °C
Device short nameNSX160F
Device applicationDistribution
Overvoltage categoryIII
Trip unit technologyThermal-magnetic
Earth-leakage protectionWithout
Suitability for isolationYes conforming to EN/IEC 60947-2
Neutral protection setting1 x Ir (4D)
Trip unit protection functionsLI
Ambient air temperature for storage-50...85 °C
Ambient air temperature for operation-25...70 °C
[Tr] Long-Time delay adjustment range120...400 s at 1.5 x In 15 s at 6 x Ir
[Ir] long-time protection pick-up adjustment range0.7...1 x In
[Ii] instantaneous protection pick-up adjustment range1250 A
MPN