Specifications

C16H32M150 key specifications
ParameterValue
Control typeToggle
Network typeAC
Protection typeL : for overload protection (long time) So : for short time short-circuit protection with fixed delay I : for instantaneous short-circuit protection
Product or component typeCircuit breaker
Long-time protection delay adjustment type trFixed
Short-time protection delay adjustment type tsdFixed
Short-time protection pick-up adjustment type isdAdjustable 9 settings
Instantaneous protection pick-up adjustment type iiFixed
Long-time pick-up adjustment type ir (thermal protection)Adjustable 9 settings
Voltage800 V AC 50/60 Hz
[Ue] rated operational voltage690 V AC 50/60 Hz
[Uimp] rated impulse withstand voltage8 kV

All specifications

C16H32M150 additional specifications
ParameterValue
Breaking capacity100 kA Icu at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 70 kA Icu at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 65 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 50 kA Icu at 500 V AC 50/60 Hz conforming to IEC 60947-2 35 kA Icu at 525 V AC 50/60 Hz conforming to IEC 60947-2 10 kA Icu at 660/690 V AC 50/60 Hz conforming to IEC 60947-2 85 kA Icu at 240 V AC 50/60 Hz conforming to UL 60947-4-1 65 kA Icu at 480 V AC 50/60 Hz conforming to UL 60947-4-1 10 kA Icu at 600 V AC 50/60 Hz conforming to UL 60947-4-1
Current150 A at 65 °C
Breaking capacity codeH 70 kA 415 V AC
[Ics] rated service breaking capacity100 kA at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 70 kA at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 65 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2 50 kA at 500 V AC 50/60 Hz conforming to IEC 60947-2 35 kA at 525 V AC 50/60 Hz conforming to IEC 60947-2 10 kA at 660/690 V AC 50/60 Hz conforming to IEC 60947-2
Power dissipation per pole9.2 W
Network frequency50/60 Hz
Poles description3P
Protected poles description3D
Utilisation categoryCategory A
IK degree of protectionIK07 conforming to IEC 62262
IP degree of protectionIP40 conforming to IEC 60529
Mounting supportBackplate
Mounting positionHorizontal and vertical Flat on the back
Circuit breaker mounting modeFixed
Connection pitch35 mm
Upside connectionFront
Downside connectionFront
Pollution degree3 conforming to IEC 60664-1
Relative humidity0...95 %
Operating altitude0...2000 m without derating 2000 m...5000 m with derating
Electrical shock protection classClass II on front face
Depth86 mm
Width105 mm
Height161 mm
Electrical durability40000 cycles at 440 V In/2 20000 cycles at 440 V In 15000 cycles at 690 V In/2 7500 cycles at 690 V In
Mechanical durability40000 cycles
StandardsEN/IEC 60947-2
RangeComPacT
Thermal memory20 minutes before and after tripping
Trip unit nameMicroLogic 2.2 M
Number of slots5 slot(s)
Local signallingFlashing LED (green) for ready to operate LED 95 % Ith (red) for temperature over set point
Trip unit rating150 A at 65 °C
Device short nameNSX160H
Device applicationMotor protection
Motor tripping class10 5 20
Overvoltage categoryIII
Trip unit technologyElectronic
Earth-leakage protectionWithout
Suitability for isolationYes conforming to EN/IEC 60947-2
Complementary motor protectionPhase unbalance
Trip unit protection functionsLSoI
Zone selective interlocking ZSIWithout
Ambient air temperature for storage-50...85 °C
Ambient air temperature for operation-25...70 °C
[Tr] Long-Time delay adjustment range120 s at 1.5 x Ir for trip class 5 6.5 s at 6 x Ir for trip class 5 5 s at 7.2 x Ir for trip class 5 240 s at 1.5 x Ir for trip class 10 13.5 s at 6 x Ir for trip class 10 10 s at 7.2 x Ir for trip class 10 480 s at 1.5 x Ir for trip class 20 26 s at 6 x Ir for trip class 20 20 s at 7.2 x Ir for trip class 20
[Ir] long-time protection pick-up adjustment range70...150 A
[Isd] short-time protection pick-up adjustment range5...13 x Ir
[Ii] instantaneous protection pick-up adjustment range2250 A
MPN