Skip to main content
Schneider Electric C16H3MA150

Schneider Electric C16H3MA150

MPNC16H3MA150
Active

C16H3MA150 - NSX160H 70KA AC 3P3D 150A MA by SCHNEIDER ELECTRIC

$471.17Ref. price · indicative, final on quote
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

C16H3MA150 key specifications
ParameterValue
Control typeToggle
Network typeAC
Protection typeI : for short-circuit protection (magnetic)
Product or component typeCircuit breaker
Short-time protection pick-up adjustment type isdAdjustable
Instantaneous protection pick-up adjustment type iiAdjustable 9 settings
Voltage800 V AC 50/60 Hz
[Ue] rated operational voltage690 V AC 50/60 Hz
[Uimp] rated impulse withstand voltage8 kV
Breaking capacity100 kA Icu at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 70 kA Icu at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 65 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 50 kA Icu at 500 V AC 50/60 Hz conforming to IEC 60947-2 35 kA Icu at 525 V AC 50/60 Hz conforming to IEC 60947-2 10 kA Icu at 660/690 V AC 50/60 Hz conforming to IEC 60947-2 85 kA Icu at 240 V AC 50/60 Hz conforming to UL 60947-4-1 65 kA Icu at 480 V AC 50/60 Hz conforming to UL 60947-4-1 10 kA Icu at 600 V AC 50/60 Hz conforming to UL 60947-4-1
Current150 A at 65 °C
Breaking capacity codeH 70 kA 415 V AC

All specifications

C16H3MA150 additional specifications
ParameterValue
[Ics] rated service breaking capacity100 kA at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 70 kA at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 65 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2 50 kA at 500 V AC 50/60 Hz conforming to IEC 60947-2 35 kA at 525 V AC 50/60 Hz conforming to IEC 60947-2 10 kA at 660/690 V AC 50/60 Hz conforming to IEC 60947-2
Power dissipation per pole8.55 W
Network frequency50/60 Hz
Poles description3P
Protected poles description3D
Utilisation categoryCategory A
IK degree of protectionIK07 conforming to IEC 62262
IP degree of protectionIP40 conforming to IEC 60529
Mounting supportBackplate
Mounting positionHorizontal and vertical Flat on the back
Circuit breaker mounting modeFixed
Connection pitch35 mm
Upside connectionFront
Downside connectionFront
Pollution degree3 conforming to IEC 60664-1
Relative humidity0...95 %
Operating altitude0...2000 m without derating 2000 m...5000 m with derating
Electrical shock protection classClass II on front face
Depth86 mm
Width105 mm
Height161 mm
Electrical durability40000 cycles at 440 V In/2 20000 cycles at 440 V In 15000 cycles at 690 V In/2 7500 cycles at 690 V In
Mechanical durability40000 cycles
StandardsEN/IEC 60947-2
RangeComPacT
Trip unit nameMA
Number of slots5 slot(s)
Trip unit rating150 A at 65 °C
Device short nameNSX160H
Device applicationMotor protection
Overvoltage categoryIII
Trip unit technologyMagnetic
Earth-leakage protectionWithout
Suitability for isolationYes conforming to EN/IEC 60947-2
Trip unit protection functionsI
Ambient air temperature for storage-50...85 °C
Ambient air temperature for operation-25...70 °C
[Isd] short-time protection pick-up adjustment range9...14 x In
[Ii] instantaneous protection pick-up adjustment range9...14 x In
MPN
C16H3MA150