Schneider Electric C16H4TM125 — Miniature Circuit Breakers (MCB)

Schneider Electric C16H4TM125 ComPacT NSX160H, 125 A, 70 kA

MPNC16H4TM125
Active

Schneider Electric ComPacT NSX, NSX160H, circuit breaker, 4P, 125 A, TM-D trip unit, 70 kA Icu at 415 V AC, IP40, front connections.

$351.82Ref. price · indicative, final on quote
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

C16H4TM125 — Identification
ParameterValue
Product nameComPacT NSX
Product rangeComPacT
Product/component typeCircuit breaker
Device applicationDistribution
C16H4TM125 — Ratings
ParameterValue
Rated current (In)125 A at 40 °C
Poles configuration4P
Breaking capacity100 kA Icu at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 70 kA Icu at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 65 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 50 kA Icu at 500 V AC 50/60 Hz conforming to IEC 60947-2 35 kA Icu at 525 V AC 50/60 Hz conforming to IEC 60947-2 10 kA Icu at 660/690 V AC 50/60 Hz conforming to IEC 60947-2 85 kA Icu at 240 V AC 50/60 Hz conforming to UL 60947-4-1 65 kA Icu at 480 V AC 50/60 Hz conforming to UL 60947-4-1 10 kA Icu at 600 V AC 50/60 Hz conforming to UL 60947-4-1
Rated service breaking capacity (Ics)100 kA at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 70 kA at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 65 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2 50 kA at 500 V AC 50/60 Hz conforming to IEC 60947-2 35 kA at 525 V AC 50/60 Hz conforming to IEC 60947-2 10 kA at 660/690 V AC 50/60 Hz conforming to IEC 60947-2
Rated operational voltage (Ue)690 V AC 50/60 Hz
Rated insulation voltage (Ui)800 V AC 50/60 Hz
Rated impulse withstand voltage (Uimp)8 kV
Network type (AC/DC)AC
Network frequency50/60 Hz
Utilisation categoryCategory A
Overvoltage categoryIII
C16H4TM125 — Protection
ParameterValue
Trip unit technologyThermal-magnetic
Earth-leakage protectionWithout
Suitability for isolationYes conforming to EN/IEC 60947-2
Electrical durability (cycles)40000 cycles at 440 V In/2 20000 cycles at 440 V In 15000 cycles at 690 V In/2 7500 cycles at 690 V In
Mechanical durability (cycles)40000 cycles
C16H4TM125 — Mechanical
ParameterValue
Mounting supportBackplate
Control typeToggle
C16H4TM125 — Environmental
ParameterValue
Operating ambient temperature-25...70 °C
Storage ambient temperature-50...85 °C
IP degree of protectionIP40 conforming to IEC 60529
Pollution degree3 conforming to IEC 60664-1
Relative humidity0...95 %
C16H4TM125 — Approvals
ParameterValue
StandardsEN/IEC 60947-2
C16H4TM125 — Specifications
ParameterValue
[Ir] long-time protection pick-up adjustment range0.7...1 x In
Trip unit protection functionsLI

Product details

The C16H4TM125: The H breaking capacity code delivers 70 kA Icu at 380/415 V AC and 100 kA Icu at 220/240 V AC, per IEC 60947-2. At 480 V AC the UL rating is 65 kA Icu. That SCCR headroom allows the NSX160H to serve as the main breaker in a panel fed by a transformer in the 500–1000 kVA range, where available fault current can exceed 50 kA. The utilisation category A means it is not intended for motor starting duty — use a motor-circuit protector (MCP) for that application.

Trip unit and protection

The thermal element tracks RMS heating in the conductor; the magnetic element responds instantaneously to a fault. The neutral protection setting is fixed at 1 x Ir (4D), meaning the neutral pole is protected at the same level as the phase poles — standard for 4-pole distribution breakers. No earth-leakage protection is integrated; add a Vigil Earth-leakage module externally if required.

Mounts on a backplate in either horizontal or vertical orientation. Front connections on both upside and downside simplify busbar and cable routing in a panel. The 140 mm width, 161 mm height, and 86 mm depth fit standard ComPacT NSX cutouts. The IP40 enclosure is suitable for indoor switchgear; IK07 impact resistance handles incidental tool contact during commissioning.

Frequently asked questions

How do I get current pricing and availability for C16H4TM125?

Submit an RFQ through this listing. Pricing and stock are confirmed at quote time; the part is sourced through independent distribution channels.

What is the breaking capacity of C16H4TM125 at 415 V?

70 kA Icu at 380/415 V AC 50/60 Hz per IEC 60947-2. At 240 V AC it is 100 kA Icu; at 690 V AC it is 10 kA Icu.

What compliance documentation does this brand provide for C16H4TM125?

The breaker is certified to EN/IEC 60947-2 and UL 60947-4-1. The IP40 and IK07 ratings conform to IEC 60529 and IEC 62262 respectively. Pollution degree 3 per IEC 60664-1 and overvoltage category III are specified. RoHS/REACH documentation is typically available from the manufacturer upon request.