Schneider Electric C16M1TM125 — Miniature Circuit Breakers (MCB)

C16M1TM125 ComPacT NSX160M 1P 125A Thermal-Magnetic MCCB, 40

MPNC16M1TM125
Active

Schneider Electric ComPacT NSX160M, 1-pole, 125 A, TM-D thermal-magnetic trip unit, 40 kA Icu at 240 V AC, fixed mount, front connections.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

C16M1TM125 — Identification
ParameterValue
Product nameComPacT NSX
Product rangeComPacT
Product/component typeCircuit breaker
Device applicationDistribution
C16M1TM125 — Ratings
ParameterValue
Rated current (In)125 A at 40 °C
Poles configuration1P
Breaking capacity40 kA Icu at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 85 kA Icu at 250 V DC conforming to IEC 60947-2
Rated service breaking capacity (Ics)40 kA at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 85 kA at 250 V DC conforming to IEC 60947-2
Rated operational voltage (Ue)277 V AC 50/60 Hz 250 V DC
Rated insulation voltage (Ui)750 V AC 50/60 Hz conforming to IEC 60947-2
Rated impulse withstand voltage (Uimp)8 kV conforming to IEC 60947-2
Network type (AC/DC)AC DC
Network frequency50/60 Hz
Utilisation categoryCategory A
Overvoltage categoryIV
C16M1TM125 — Protection
ParameterValue
Trip unit technologyThermal-magnetic
Earth-leakage protectionWithout
Suitability for isolationYes conforming to EN/IEC 60947-2
Electrical durability (cycles)20000 cycles at 277 V In/2 10000 cycles at 277 V In
Mechanical durability (cycles)20000 cycles
C16M1TM125 — Mechanical
ParameterValue
Mounting supportBackplate
Control typeToggle
C16M1TM125 — Environmental
ParameterValue
Operating ambient temperature-25...70 °C
Storage ambient temperature-50...85 °C
IP degree of protectionIP40 conforming to IEC 60529
Pollution degree3 conforming to IEC 60664-1
Relative humidity0...95 %
C16M1TM125 — Approvals
ParameterValue
StandardsEN/IEC 60947-2
C16M1TM125 — Specifications
ParameterValue
[Ir] long-time protection pick-up adjustment range1 x In
Trip unit protection functionsLI

Product details

The C16M1TM125 is a fixed-mount 1-pole ComPacT NSX160M moulded-case circuit breaker with a TM-D thermal-magnetic trip unit rated 125 A at 40 °C. It belongs to the ComPacT range and is designed for distribution applications per EN/IEC 60947-2. The breaking capacity is 40 kA Icu at 240 V AC and 85 kA Icu at 250 V DC, both conforming to IEC 60947-2. The 85 kA DC rating is unusually high for a 1-pole frame; it makes this breaker a candidate for DC bus or battery-string protection where high prospective fault currents exist. It is a Category A breaker (no intentional short-time delay), so it opens instantaneously on magnetic pickup. Overvoltage category IV means it is rated for installation at the origin of the installation (utility entrance or main distribution), not just downstream subpanels.

Mounting and connections

Mounts fixed to a backplate in either horizontal or vertical orientation. Width is 35 mm (one 35 mm pitch), height 161 mm, depth 86 mm. Both line and load connections are front-accessible — no rear bus adaptors needed. The 35 mm connection pitch matches standard DIN-rail terminal blocks for straightforward panel wiring. IP40 enclosure protection (tools and small wires only, no water ingress) and IK07 impact resistance.

Suitability for isolation is confirmed per EN/IEC 60947-2, meaning it provides a visible break and meets the isolation requirements for safe maintenance access downstream.

Durability and dissipation

Mechanical endurance is 20,000 cycles; electrical endurance is 20,000 cycles at 277 V at In/2 and 10,000 cycles at 277 V at full rated current In.

Frequently asked questions

Where can I buy C16M1TM125 and what is the lead time?

This part is sourced to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time — submit an RFQ for the current lead time and price.

What is the closest alternative to C16M1TM125 in the ComPacT family?

Within the same NSX160M frame, the closest alternative would be a different trip unit rating or a different breaking capacity code (e.g., NSX160M with an F or H breaking capacity). The C16M1TM125 is the 125 A TM-D version; if you need electronic trip or earth-leakage protection, you would move to the Micrologic trip unit variants in the same frame size.

What compliance documentation does Schneider provide for C16M1TM125?

The breaker is certified to EN/IEC 60947-2 and carries a CE marking for the European market. It is suitable for isolation per that standard. For specific RoHS, REACH, or UL documentation, request the manufacturer's declaration of compliance with your RFQ.

MPN