Skip to main content
Schneider Electric C16N1TM125

Schneider C16N1TM125 ComPacT NSX MCCB, 1-pole, 125 A, 25 kA

MPNC16N1TM125
Obsolete

Schneider ComPacT NSX C16N1TM125 molded case circuit breaker, 1-pole, 125 A, 25 kA IC at 277 V AC, thermal-magnetic TM-D trip unit, fixed mount, toggle control, EN/IEC 60947-2.

$343.00 – $363.29Ref. price · indicative, final on quote
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

C16N1TM125 key specifications
ParameterValue
Control typeToggle
Network typeAC DC
Protection typeL : for overload protection (thermal) I : for short-circuit protection (magnetic)
Product or component typeCircuit breaker
Long-time protection delay adjustment type trFixed
Instantaneous protection pick-up adjustment type iiFixed
Long-time pick-up adjustment type ir (thermal protection)Fixed
Voltage750 V AC 50/60 Hz conforming to IEC 60947-2
[Ue] rated operational voltage277 V AC 50/60 Hz 250 V DC
[Uimp] rated impulse withstand voltage8 kV conforming to IEC 60947-2
Breaking capacity25 kA Icu at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 50 kA Icu at 250 V DC conforming to IEC 60947-2
Current125 A at 40 °C

All specifications

C16N1TM125 additional specifications
ParameterValue
Breaking capacity codeN 25 kA 240 V AC
[Ics] rated service breaking capacity25 kA at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 50 kA at 250 V DC conforming to IEC 60947-2
Power dissipation per pole10.78 W
Network frequency50/60 Hz
Poles description1P
Protected poles description1D
Utilisation categoryCategory A
IK degree of protectionIK07 conforming to IEC 62262
IP degree of protectionIP40 conforming to IEC 60529
Mounting supportBackplate
Mounting positionHorizontal and vertical Flat on the back
Circuit breaker mounting modeFixed
Connection pitch35 mm
Upside connectionFront
Downside connectionFront
Pollution degree3 conforming to IEC 60664-1
Relative humidity0...95 %
Operating altitude0...2000 m without derating 2000 m...5000 m with derating
Electrical shock protection classClass II on front face
Depth86 mm
Width35 mm
Height161 mm
Electrical durability20000 cycles at 277 V In/2 10000 cycles at 277 V In
Mechanical durability20000 cycles
StandardsEN/IEC 60947-2
RangeComPacT
Trip unit nameTM-D
Trip unit rating125 A at 40 °C
Device short nameNSX160N
Device applicationDistribution
Overvoltage categoryIV
Trip unit technologyThermal-magnetic
Earth-leakage protectionWithout
Suitability for isolationYes conforming to EN/IEC 60947-2
Trip unit protection functionsLI
Ambient air temperature for storage-50...85 °C
Ambient air temperature for operation-25...70 °C
[Ir] long-time protection pick-up adjustment range1 x In
[Ii] instantaneous protection pick-up adjustment range1000 A

Product details

Overview

The C16N1TM125 is a Schneider ComPacT NSX molded case circuit breaker rated 125 A at 40 °C with a breaking capacity of 25 kA at 277 V AC. This 1-pole unit uses a thermal-magnetic TM-D trip unit providing LI protection (overload and short-circuit). It is in active production.

Schneider lists the C16N1TM125 as an active, current-production part within the ComPacT NSX range. Standard lead times apply through distribution; submit an RFQ for current pricing and availability.

MPN
C16N1TM125