Skip to main content
Schneider Electric C16S2TM125 — Miniature Circuit Breakers (MCB)

Schneider Electric C16S2TM125 ComPacT NSX160S, 125 A, 2P MCC

MPNC16S2TM125
Obsolete

Schneider Electric ComPacT NSX160S, C16S2TM125, 2-pole MCCB, 125 A thermal-magnetic trip unit, 70 kA breaking capacity at 415 V AC.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

C16S2TM125 — Identification
ParameterValue
Product nameComPacT NSX
Product rangeComPacT
Product/component typeCircuit breaker
Device applicationDistribution
C16S2TM125 — Ratings
ParameterValue
Rated current (In)125 A at 40 °C
Poles configuration2P
Breaking capacity100 kA Icu at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 70 kA Icu at 380/415 V AC 50/60 Hz 1P conforming to IEC 60947-2 65 kA Icu at 440 V AC 50/60 Hz 1P conforming to IEC 60947-2 35 kA Icu at 500/525 V AC 50/60 Hz 2P conforming to IEC 60947-2 10 kA Icu at 660/690 V AC 50/60 Hz conforming to IEC 60947-2 100 kA Icu at 250 V DC 50/60 Hz 1 pole conforming to IEC 60947-2 100 kA Icu at 500 V DC 50/60 Hz 2 poles in series conforming to IEC 60947-2
Rated service breaking capacity (Ics)100 kA at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 70 kA at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 65 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2 35 kA at 500/525 V AC 50/60 Hz conforming to IEC 60947-2 10 kA at 660/690 V AC 50/60 Hz conforming to IEC 60947-2 100 kA at 250 V DC 50/60 Hz conforming to IEC 60947-2 100 kA at 500 V DC 50/60 Hz conforming to IEC 60947-2
Rated operational voltage (Ue)690 V AC 50/60 Hz 500 V DC
Rated insulation voltage (Ui)750 V AC 50/60 Hz conforming to IEC 60947-2
Rated impulse withstand voltage (Uimp)8 kV conforming to IEC 60947-2
Network type (AC/DC)AC DC
Network frequency50/60 Hz
Utilisation categoryCategory A
Overvoltage categoryIII
C16S2TM125 — Protection
ParameterValue
Trip unit technologyThermal-magnetic
Earth-leakage protectionWithout
Suitability for isolationYes conforming to EN/IEC 60947-2
Electrical durability (cycles)20000 cycles at 277 V In/2 10000 cycles at 277 V In
Mechanical durability (cycles)20000 cycles
C16S2TM125 — Mechanical
ParameterValue
Mounting supportBackplate
Control typeToggle
C16S2TM125 — Environmental
ParameterValue
Operating ambient temperature-25...70 °C
Storage ambient temperature-50...85 °C
IP degree of protectionIP40 conforming to IEC 60529
Pollution degree3 conforming to IEC 60664-1
Relative humidity0...95 %
C16S2TM125 — Approvals
ParameterValue
StandardsEN/IEC 60947-2
C16S2TM125 — Specifications
ParameterValue
[Ir] long-time protection pick-up adjustment range1 x In
Trip unit protection functionsLI

Product details

What the ratings mean for your panel

The C16S2TM125 is a ComPacT NSX160S frame 2-pole MCCB with a TM-D thermal-magnetic trip unit rated 125 A at 40 °C. The S breaking capacity code means 70 kA Icu at 415 V AC — that's the fault current it can safely interrupt without welding contacts or rupturing the case, sized for high-fault distribution panels where upstream transformer capacity is substantial. At 240 V AC it delivers the full 100 kA Icu, so it also handles industrial service-entrance duty where the utility fault level is high. The thermal-magnetic trip (TM-D) gives two protection curves in one device: the thermal element handles overload protection (L) with an inverse-time characteristic that mimics cable heating, and the magnetic element provides instantaneous short-circuit protection (I) that clears bolted faults fast. No earth-leakage function built in — if you need that, add a Vigi module externally. Rated for isolation per EN/IEC 60947-2, so it can serve as a visible-break disconnect when locked off. Pollution degree 3 and overvoltage category III mean it's rated for industrial environments where conductive dust and switching transients are normal — not just clean commercial switchgear.

Mounting and integration

Fixed-mount backplate installation, 70 mm wide, 161 mm tall, 86 mm deep — fits standard panel cutouts for the NSX160S frame. Front connections both top and bottom, with a 35 mm connection pitch that matches busbar systems and lug kits. IP40 enclosure rating means it's protected against tools and wires >1 mm but not washdown; keep it inside a panel or enclosure. Mounts horizontally or vertically flat on the backplate — no derating required for orientation. Operating altitude up to 2000 m without derating; above that, up to 5000 m with derating applied per IEC 60947-2. Ambient humidity range 0–95 % non-condensing.

Frequently asked questions

Where can I buy C16S2TM125 and get a price?

Sourced and quoted to order against an RFQ through independent distribution channels. Submit a request for quote to confirm current availability and pricing.

What breaking capacity does C16S2TM125 have at 415 V?

70 kA Icu at 380/415 V AC, 1-pole per IEC 60947-2. For a 2-pole connection at 415 V, the full 70 kA applies across both poles in series.

What standards does C16S2TM125 comply with?

Designed and tested to EN/IEC 60947-2 for low-voltage switchgear and controlgear. Rated for isolation per the same standard, with pollution degree 3 and overvoltage category III.

MPN
C16S2TM125