Schneider Electric C16F2TM125 — Miniature Circuit Breakers (MCB)

Schneider Electric C16F2TM125 ComPacT NSX160F, 125A, 18kA 41

MPNC16F2TM125
Active

Schneider Electric ComPacT NSX160F, C16F2TM125, 2-pole circuit breaker, 125 A thermal-magnetic trip unit, 18 kA Icu at 415 V AC, IEC 60947-2.

$3.91Ref. price · indicative, final on quote
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

C16F2TM125 — Identification
ParameterValue
Product nameComPacT NSX
Product rangeComPacT
Product/component typeCircuit breaker
Device applicationDistribution
C16F2TM125 — Ratings
ParameterValue
Rated current (In)125 A at 40 °C
Poles configuration2P
Breaking capacity36 kA Icu at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 18 kA Icu at 380/415 V AC 50/60 Hz 1P conforming to IEC 60947-2 15 kA Icu at 440 V AC 50/60 Hz 1P conforming to IEC 60947-2 10 kA Icu at 500/525 V AC 50/60 Hz 2P conforming to IEC 60947-2 5 kA Icu at 660/690 V AC 50/60 Hz conforming to IEC 60947-2 36 kA Icu at 250 V DC 50/60 Hz 1 pole conforming to IEC 60947-2 36 kA Icu at 500 V DC 50/60 Hz 2 poles in series conforming to IEC 60947-2
Rated service breaking capacity (Ics)36 kA at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 18 kA at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 15 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2 10 kA at 500/525 V AC 50/60 Hz conforming to IEC 60947-2 5 kA at 660/690 V AC 50/60 Hz conforming to IEC 60947-2 36 kA at 250 V DC 50/60 Hz conforming to IEC 60947-2 36 kA at 500 V DC 50/60 Hz conforming to IEC 60947-2
Rated operational voltage (Ue)690 V AC 50/60 Hz 500 V DC
Rated insulation voltage (Ui)750 V AC 50/60 Hz conforming to IEC 60947-2
Rated impulse withstand voltage (Uimp)8 kV conforming to IEC 60947-2
Network type (AC/DC)AC DC
Network frequency50/60 Hz
Utilisation categoryCategory A
Overvoltage categoryIII
C16F2TM125 — Protection
ParameterValue
Trip unit technologyThermal-magnetic
Earth-leakage protectionWithout
Suitability for isolationYes conforming to EN/IEC 60947-2
Electrical durability (cycles)20000 cycles at 277 V In/2 10000 cycles at 277 V In
Mechanical durability (cycles)20000 cycles
C16F2TM125 — Mechanical
ParameterValue
Mounting supportBackplate
Control typeToggle
C16F2TM125 — Environmental
ParameterValue
Operating ambient temperature-25...70 °C
Storage ambient temperature-50...85 °C
IP degree of protectionIP40 conforming to IEC 60529
Pollution degree3 conforming to IEC 60664-1
Relative humidity0...95 %
C16F2TM125 — Approvals
ParameterValue
StandardsEN/IEC 60947-2
C16F2TM125 — Specifications
ParameterValue
[Ir] long-time protection pick-up adjustment range1 x In
Trip unit protection functionsLI

Product details

The Schneider Electric C16F2TM125 is a ComPacT NSX160F fixed-mount circuit breaker, 2-pole, with a TM-D thermal-magnetic trip unit rated 125 A at 40 °C. It belongs to the ComPacT NSX family, the modular molded-case line that replaced the older Compact NS series on most BOMs.

At 220/240 V AC the breaker clears 36 kA; at 440 V it drops to 15 kA, and at 690 V to 5 kA. On DC, 36 kA at 250 V DC (1 pole) and 36 kA at 500 V DC (2 poles in series). The 125 A TM-D trip provides L (thermal overload) and I (magnetic short-circuit) protection — no earth-leakage module. For a 125 A feeder on a 415 V system, this breaker coordinates downstream with 63 A or 100 A NSX breakers using the manufacturer's selectivity tables.

Fixed-mount on a backplate, 70 mm wide, 161 mm high, 86 mm deep. Front-connect for both line and load. IP40 enclosure protection, IK07 impact resistance. Rated for 0 to 2000 m altitude without derating, 2000 to 5000 m with derating. 0 to 95 % relative humidity.

Endurance and dissipation

Mechanical durability: 20,000 cycles. Electrical durability: 20,000 cycles at 277 V at half rated current, 10,000 cycles at full rated current. Power dissipation per pole is 10.78 W — useful for thermal calculations in a sealed enclosure.

Frequently asked questions

How do I get pricing and availability for C16F2TM125?

Pricing and availability are confirmed at quote time against an RFQ through independent distribution channels.

What is the breaking capacity of C16F2TM125 at 415 V?

18 kA Icu at 380/415 V AC, 50/60 Hz, 1-pole, per IEC 60947-2.

What compliance standards does C16F2TM125 meet?

Certified to EN/IEC 60947-2, suitable for isolation per that standard. Pollution degree 3 per IEC 60664-1, overvoltage category III.

MPN
C16F2TM125