Specifications

C25B3TM250 key specifications
ParameterValue
Control typeToggle
Network typeAC
Protection typeL : for overload protection (thermal) I : for short-circuit protection (magnetic)
Product or component typeCircuit breaker
Long-time protection delay adjustment type trFixed
Instantaneous protection pick-up adjustment type iiAdjustable
Long-time pick-up adjustment type ir (thermal protection)Adjustable
Voltage800 V AC 50/60 Hz
[Ue] rated operational voltage690 V AC 50/60 Hz
[Uimp] rated impulse withstand voltage8 kV
Breaking capacity40 kA Icu at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 25 kA Icu at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 20 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 15 kA Icu at 500 V AC 50/60 Hz conforming to IEC 60947-2
Current250 A at 40 °C

All specifications

C25B3TM250 additional specifications
ParameterValue
Breaking capacity codeB 25 kA 415 V AC
[Ics] rated service breaking capacity40 kA at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 25 kA at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 20 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2 15 kA at 500 V AC 50/60 Hz conforming to IEC 60947-2
Power dissipation per pole18.75 W
Network frequency50/60 Hz
Poles description3P
Protected poles description3D
Utilisation categoryCategory A
IK degree of protectionIK07 conforming to IEC 62262
IP degree of protectionIP40 conforming to IEC 60529
Mounting supportBackplate
Mounting positionHorizontal and vertical Flat on the back
Circuit breaker mounting modeFixed
Connection pitch35 mm
Upside connectionFront
Downside connectionFront
Pollution degree3 conforming to IEC 60664-1
Relative humidity0...95 %
Operating altitude0...2000 m without derating 2000 m...5000 m with derating
Electrical shock protection classClass II on front face
Depth86 mm
Width105 mm
Height161 mm
Electrical durability20000 cycles at 440 V In/2 10000 cycles at 440 V In 10000 cycles at 690 V In/2 5000 cycles at 690 V In
Mechanical durability20000 cycles
StandardsEN/IEC 60947-2
RangeComPacT
Trip unit nameTM-D
Number of slots5 slot(s)
Trip unit rating250 A at 40 °C
Device short nameNSX250B
Device applicationDistribution
Overvoltage categoryIII
Trip unit technologyThermal-magnetic
Earth-leakage protectionWithout
Suitability for isolationYes conforming to EN/IEC 60947-2
Trip unit protection functionsLI
Ambient air temperature for storage-50...85 °C
Ambient air temperature for operation-25...70 °C
[Tr] Long-Time delay adjustment range120...400 s at 1.5 x In 15 s at 6 x Ir
[Ir] long-time protection pick-up adjustment range0.7...1 x In
[Ii] instantaneous protection pick-up adjustment range5...10 x In
MPN