Skip to main content
Schneider Electric C25B4TM200C — Miniature Circuit Breakers (MCB)

C25B4TM200C ComPacT NSX250B 4P 200A Breaker, 25 kA 415V

MPNC25B4TM200C
Active

Schneider Electric ComPacT NSX250B, 4-pole, 200 A thermal-magnetic circuit breaker, TM-D trip unit, 25 kA breaking capacity at 415 V AC, IP40, backplate mount.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

C25B4TM200C — Identification
ParameterValue
Product nameComPacT NSX
Product rangeComPacT
Product/component typeCircuit breaker
Device applicationDistribution
C25B4TM200C — Ratings
ParameterValue
Rated current (In)200 A at 50 °C
Poles configuration4P
Breaking capacity40 kA Icu at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 25 kA Icu at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 20 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 15 kA Icu at 500 V AC 50/60 Hz conforming to IEC 60947-2
Rated service breaking capacity (Ics)40 kA at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 25 kA at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 20 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2 15 kA at 500 V AC 50/60 Hz conforming to IEC 60947-2
Rated operational voltage (Ue)690 V AC 50/60 Hz
Rated insulation voltage (Ui)800 V AC 50/60 Hz
Rated impulse withstand voltage (Uimp)8 kV
Network type (AC/DC)AC
Network frequency50/60 Hz
Utilisation categoryCategory A
Overvoltage categoryIII
C25B4TM200C — Protection
ParameterValue
Trip unit technologyThermal-magnetic
Earth-leakage protectionWithout
Suitability for isolationYes conforming to EN/IEC 60947-2
Electrical durability (cycles)20000 cycles at 440 V In/2 10000 cycles at 440 V In 10000 cycles at 690 V In/2 5000 cycles at 690 V In
Mechanical durability (cycles)20000 cycles
C25B4TM200C — Mechanical
ParameterValue
Mounting supportBackplate
Control typeToggle
C25B4TM200C — Environmental
ParameterValue
Operating ambient temperature-25...70 °C
Storage ambient temperature-50...85 °C
IP degree of protectionIP40 conforming to IEC 60529
Pollution degree3 conforming to IEC 60664-1
Relative humidity0...95 %
C25B4TM200C — Approvals
ParameterValue
StandardsEN/IEC 60947-2
C25B4TM200C — Specifications
ParameterValue
[Ir] long-time protection pick-up adjustment range0.7...1 x In
Trip unit protection functionsLI

Product details

The C25B4TM200C is a Schneider Electric ComPacT NSX250B 4-pole moulded-case circuit breaker with a TM-D thermal-magnetic trip unit rated 200 A at 50 °C. The TM-D trip gives you fixed thermal protection for overloads (the L curve) and fixed magnetic protection for short circuits (the I curve), which means no adjustment dials to set; it's a straightforward, no-nonsense choice for a standard distribution application where you don't need electronic tuning. The breaking capacity is 25 kA Icu at 380/415 V AC 50/60 Hz per IEC 60947-2, with higher ratings at lower voltages — 40 kA at 220/240 V and 20 kA at 440 V.

Mounts on a backplate — no DIN rail here, so plan for bolt-down installation. The 4-pole footprint means it takes up a full four-module width in a distribution board. Both line and load connections are front-facing, which keeps wiring accessible in a tight cabinet.

What else to know

Mechanical durability is rated at 20,000 cycles; electrical durability varies with load — 20,000 cycles at half-rated current, 10,000 at full rated current. No earth-leakage protection built in; if you need that, you'll add a Vigi module externally.

Frequently asked questions

What is the breaking capacity of C25B4TM200C at 415 V?

The C25B4TM200C has a breaking capacity of 25 kA Icu at 380/415 V AC per IEC 60947-2. At 220/240 V it's 40 kA; at 440 V it's 20 kA; at 500 V it's 15 kA.

Where can I buy C25B4TM200C and get a quote?

C25B4TM200C is sourced and quoted to order against an RFQ through our independent distribution. Availability and current pricing are confirmed at quote time — submit an RFQ for a firm price and lead time.

What standards does C25B4TM200C comply with?

The C25B4TM200C is certified to EN/IEC 60947-2 for circuit breakers, rated for isolation under that standard. It also meets IEC 60664-1 pollution degree 3 and IEC 62262 IK07 impact resistance.

MPN