The C25B3TM125C is a Schneider Electric ComPacT NSX250B moulded-case circuit breaker, 3-pole, rated 125 A at 50 °C with a TM-D thermal-magnetic trip unit. Its breaking capacity is 25 kA Icu at 380/415 V AC 50/60 Hz per IEC 60947-2, with a code B rating (25 kA at 415 V). The TM-D trip gives you fixed thermal (L) overload protection and fixed magnetic (I) short-circuit protection — no adjustment dials. At 125 A and 50 °C ambient, it's sized for a downstream load like a sub-distribution board or a large motor control centre feeder.
The 105 mm width, 161 mm height, and 86 mm depth fit standard distribution board cutouts. Front connections top and bottom simplify busbar and cable routing. IP40 enclosure protection keeps dust out; IK07 impact rating handles incidental contact in a panel.