Skip to main content
Schneider Electric C25F3TM250

Schneider Electric C25F3TM250

MPNC25F3TM250
Active

NSX250F 36KA AC 3P3D 250A TMD|NSX250F 36KA AC 3P3D 250A TMD

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

C25F3TM250 key specifications
ParameterValue
Control typeToggle
Network typeAC
Protection typeL : for overload protection (thermal) I : for short-circuit protection (magnetic)
Product or component typeCircuit breaker
Long-time protection delay adjustment type trFixed
Instantaneous protection pick-up adjustment type iiAdjustable
Long-time pick-up adjustment type ir (thermal protection)Adjustable
Voltage800 V AC 50/60 Hz
[Ue] rated operational voltage690 V AC 50/60 Hz
[Uimp] rated impulse withstand voltage8 kV
Breaking capacity85 kA Icu 220/240 V AC 50/60 Hz IEC 60947-2 36 kA Icu 380/415 V AC 50/60 Hz IEC 60947-2 35 kA Icu 440 V AC 50/60 Hz IEC 60947-2 30 kA Icu 500 V AC 50/60 Hz IEC 60947-2 22 kA Icu 525 V AC 50/60 Hz IEC 60947-2 8 kA Icu 660/690 V AC 50/60 Hz IEC 60947-2 85 kA Icu 240 V AC 50/60 Hz UL 60947-4-1 35 kA Icu 480 V AC 50/60 Hz UL 60947-4-1 15 kA Icu 600 V AC 50/60 Hz UL 60947-4-1
Line rated current250 A 104 °F (40 °C)

All specifications

C25F3TM250 additional specifications
ParameterValue
Breaking capacity codeF 36 kA 415 V AC
[Ics] rated service breaking capacity85 kA 220/240 V AC 50/60 Hz IEC 60947-2 36 kA 380/415 V AC 50/60 Hz IEC 60947-2 35 kA 440 V AC 50/60 Hz IEC 60947-2 30 kA 500 V AC 50/60 Hz IEC 60947-2 22 kA 525 V AC 50/60 Hz IEC 60947-2 8 kA 660/690 V AC 50/60 Hz IEC 60947-2
Power dissipation per pole18.75 W
Network frequency50/60 Hz
Poles description3P
Protected poles description3D
Utilisation categoryCategory A
IK degree of protectionIK07 conforming to IEC 62262
IP degree of protectionIP40 conforming to IEC 60529
Mounting supportBackplate
Mounting positionHorizontal and vertical Flat on the back
Circuit breaker mounting modeFixed
Connection pitch1.4 in (35 mm)
Upside connectionFront
Downside connectionFront
Pollution degree3 IEC 60664-1
Relative humidity0...95 %
Operating altitude0...6561.68 ft (0...2000 m) without derating 2000 m...5000 m with derating
Electrical shock protection classClass II front face
Depth3.4 in (86 mm)
Width4.1 in (105 mm)
Height6.3 in (161 mm)
Electrical durability20000 cycles 440 V In/2 10000 cycles 440 V In 10000 cycles 690 V In/2 5000 cycles 690 V In
Mechanical durability20000 cycles
StandardsEN/IEC 60947-2
RangeComPacT
CategoryUS10DE201101
Trip unit nameTM-D
Number of slots5
Trip unit rating250 A 104 °F (40 °C)
Device short nameNSX250F
Device applicationDistribution
Overvoltage categoryIII
Trip unit technologyThermal-magnetic
Earth-leakage protectionWithout
Suitability for isolationYes EN/IEC 60947-2
Trip unit protection functionsLI
Ambient air temperature for storage-58...185 °F (-50...85 °C)
Ambient air temperature for operation-13...158 °F (-25...70 °C)
[Tr] Long-Time delay adjustment range120...400 s 1.5 x In 15 s 6 x Ir
[Ir] long-time protection pick-up adjustment range0.7...1 x In
[Ii] instantaneous protection pick-up adjustment range5...10 x In
MPN