Skip to main content
Schneider Electric C25F4TM200D3

Schneider Electric C25F4TM200D3

MPNC25F4TM200D3
Active

C25F4TM200D3 by SQUARE D

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

C25F4TM200D3 key specifications
ParameterValue
Control typeToggle
Network typeDC
Protection typeL : for overload protection (thermal) I : for short-circuit protection (magnetic)
Product or component typeCircuit breaker
Long-time protection delay adjustment type trFixed
Instantaneous protection pick-up adjustment type iiFixed
Long-time pick-up adjustment type ir (thermal protection)Adjustable
Voltage1600 V DC conforming to IEC 60947-2
[Ue] rated operational voltage1500 V DC
[Uimp] rated impulse withstand voltage8 kV conforming to IEC 60947-2
Breaking capacity20 kA Icu at 1500 V DC 4 poles in series conforming to IEC 60947-2 50 kA Icu at 1100 V DC 4 poles in series conforming to IEC 60947-2
Current200 A at 40 °C

All specifications

C25F4TM200D3 additional specifications
ParameterValue
Breaking capacity codeF 20 kA 1500 V DC
[Ics] rated service breaking capacity20 kA at 1500 V DC conforming to IEC 60947-2 20 kA at 1100 V DC conforming to IEC 60947-2
Poles description4P
Protected poles description4D
Utilisation categoryCategory A
IK degree of protectionIK07 conforming to IEC 62262
IP degree of protectionIP40 conforming to IEC 60529
Mounting supportBackplate
Mounting positionHorizontal and vertical Flat on the back
Circuit breaker mounting modeFixed
Upside connectionFront
Downside connectionFront
Pollution degree3 conforming to IEC 60664-1
Relative humidity0...95 %
Operating altitude0...2000 m without derating 2000 m...5000 m with derating
Depth86 mm
Width140 mm
Height161 mm
Electrical durability4500 cycles at 1500 V In
Mechanical durability10000 cycles
StandardsEN/IEC 60947-2
RangeComPacT
Trip unit nameTM-DC
Trip unit rating200 A at 40 °C
Device short nameNSX250 DC EP
Device applicationSpecial application
Trip unit technologyThermal-magnetic
Suitability for isolationYes conforming to EN/IEC 60947-2
Trip unit protection functionsLI
Ambient air temperature for storage-50...85 °C
Ambient air temperature for operation-25...70 °C
[Ir] long-time protection pick-up adjustment range0.7...1 x In
[Ii] instantaneous protection pick-up adjustment range1200 A
MPN
C25F4TM200D3