Schneider Electric C25H6TM160C — Miniature Circuit Breakers (MCB)

C25H6TM160C ComPacT NSX250H MCCB, 160 A, 70 kA at 415 V

MPNC25H6TM160C
Obsolete

Schneider Electric ComPacT NSX, NSX250H, 4P, 160 A thermal-magnetic TM-D trip, 70 kA Icu at 415 V AC, toggle control, IP40.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

C25H6TM160C — Identification
ParameterValue
Product nameComPacT NSX
Product rangeComPacT
Product/component typeCircuit breaker
Device applicationDistribution
C25H6TM160C — Ratings
ParameterValue
Rated current (In)160 A at 50 °C
Poles configuration4P
Breaking capacity100 kA Icu at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 70 kA Icu at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 65 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 50 kA Icu at 500 V AC 50/60 Hz conforming to IEC 60947-2 35 kA Icu at 525 V AC 50/60 Hz conforming to IEC 60947-2 10 kA Icu at 660/690 V AC 50/60 Hz conforming to IEC 60947-2
Rated service breaking capacity (Ics)100 kA at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 70 kA at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 65 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2 50 kA at 500 V AC 50/60 Hz conforming to IEC 60947-2 35 kA at 525 V AC 50/60 Hz conforming to IEC 60947-2 10 kA at 660/690 V AC 50/60 Hz conforming to IEC 60947-2
Rated operational voltage (Ue)690 V AC 50/60 Hz
Rated insulation voltage (Ui)800 V AC 50/60 Hz
Rated impulse withstand voltage (Uimp)8 kV
Network type (AC/DC)AC
Network frequency50/60 Hz
Utilisation categoryCategory A
Overvoltage categoryIII
C25H6TM160C — Protection
ParameterValue
Trip unit technologyThermal-magnetic
Earth-leakage protectionWithout
Suitability for isolationYes conforming to EN/IEC 60947-2
Electrical durability (cycles)20000 cycles at 440 V In/2 10000 cycles at 440 V In 10000 cycles at 690 V In/2 5000 cycles at 690 V In
Mechanical durability (cycles)20000 cycles
C25H6TM160C — Mechanical
ParameterValue
Mounting supportBackplate
Control typeToggle
C25H6TM160C — Environmental
ParameterValue
Operating ambient temperature-25...70 °C
Storage ambient temperature-50...85 °C
IP degree of protectionIP40 conforming to IEC 60529
Pollution degree3 conforming to IEC 60664-1
Relative humidity0...95 %
C25H6TM160C — Approvals
ParameterValue
StandardsEN/IEC 60947-2
C25H6TM160C — Specifications
ParameterValue
[Ir] long-time protection pick-up adjustment range0.7...1 x In
Trip unit protection functionsLI

Product details

The C25H6TM160C is a 4-pole ComPacT NSX250H moulded-case circuit breaker with a thermal-magnetic TM-D trip unit rated 160 A at 50 °C. At 220/240 V the same breaker is rated 100 kA Icu, so it handles high-fault points near the service entrance without cascading upstream. No earth-leakage module is integrated, so if ground-fault protection is required on the distribution board, a separate Vigi add-on or external relay is needed.

Front connections both top and bottom simplify bus-bar and cable routing in a distribution panel. The 140 mm width and 161 mm height fit standard ComPacT NSX cutouts; depth is 86 mm. IK07 impact resistance handles incidental tool contact during panel work.

Rated for 20,000 mechanical cycles and 20,000 electrical cycles at 440 V at rated current (In). At half-load (In/2) at 440 V, electrical durability doubles to 20,000 cycles. At 690 V, expect 5,000 cycles at In. These figures matter for frequent switching applications like capacitor bank or lighting contactor duty — if the breaker cycles daily, the mechanical endurance sets the replacement interval.

Frequently asked questions

How do I get current pricing and availability for C25H6TM160C?

Submit an RFQ through this listing. Pricing and availability are confirmed at quote time through independent distribution channels.

What is C25H6TM160C's breaking capacity at 415 V?

70 kA Icu at 380/415 V AC 50/60 Hz per IEC 60947-2. The H breaking capacity code also gives 100 kA at 220/240 V and 10 kA at 690 V.

What compliance standards does C25H6TM160C meet?

It is designed and tested to EN/IEC 60947-2 for circuit-breaker performance, suitable for isolation per that standard. Pollution degree 3 per IEC 60664-1, IP40 per IEC 60529, IK07 per IEC 62262.