Schneider Electric C25H6TM200 — Miniature Circuit Breakers (MCB)

Schneider Electric C25H6TM200 ComPacT NSX250H, 200A, 4P, 70k

MPNC25H6TM200
Active

Schneider Electric ComPacT NSX, C25H6TM200, NSX250H, 200 A, 4P, thermal-magnetic trip unit TM-D, 70 kA Icu at 415 V AC.

$526.85Ref. price · indicative, final on quote
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

C25H6TM200 — Identification
ParameterValue
Product nameComPacT NSX
Product rangeComPacT
Product/component typeCircuit breaker
Device applicationDistribution
C25H6TM200 — Ratings
ParameterValue
Rated current (In)200 A at 40 °C
Poles configuration4P
Breaking capacity100 kA Icu at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 70 kA Icu at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 65 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 50 kA Icu at 500 V AC 50/60 Hz conforming to IEC 60947-2 35 kA Icu at 525 V AC 50/60 Hz conforming to IEC 60947-2 10 kA Icu at 660/690 V AC 50/60 Hz conforming to IEC 60947-2 85 kA Icu at 240 V AC 50/60 Hz conforming to UL 60947-4-1 65 kA Icu at 480 V AC 50/60 Hz conforming to UL 60947-4-1 15 kA Icu at 600 V AC 50/60 Hz conforming to UL 60947-4-1
Rated service breaking capacity (Ics)100 kA at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 70 kA at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 65 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2 50 kA at 500 V AC 50/60 Hz conforming to IEC 60947-2 35 kA at 525 V AC 50/60 Hz conforming to IEC 60947-2 10 kA at 660/690 V AC 50/60 Hz conforming to IEC 60947-2
Rated operational voltage (Ue)690 V AC 50/60 Hz
Rated insulation voltage (Ui)800 V AC 50/60 Hz
Rated impulse withstand voltage (Uimp)8 kV
Network type (AC/DC)AC
Network frequency50/60 Hz
Utilisation categoryCategory A
Overvoltage categoryIII
C25H6TM200 — Protection
ParameterValue
Trip unit technologyThermal-magnetic
Earth-leakage protectionWithout
Suitability for isolationYes conforming to EN/IEC 60947-2
Electrical durability (cycles)20000 cycles at 440 V In/2 10000 cycles at 440 V In 10000 cycles at 690 V In/2 5000 cycles at 690 V In
Mechanical durability (cycles)20000 cycles
C25H6TM200 — Mechanical
ParameterValue
Mounting supportBackplate
Control typeToggle
C25H6TM200 — Environmental
ParameterValue
Operating ambient temperature-25...70 °C
Storage ambient temperature-50...85 °C
IP degree of protectionIP40 conforming to IEC 60529
Pollution degree3 conforming to IEC 60664-1
Relative humidity0...95 %
C25H6TM200 — Approvals
ParameterValue
StandardsEN/IEC 60947-2
C25H6TM200 — Specifications
ParameterValue
[Ir] long-time protection pick-up adjustment range0.7...1 x In
Trip unit protection functionsLI

Product details

The TM-D provides L (overload, thermal) and I (short-circuit, magnetic) protection per EN/IEC 60947-2. For a 480 V AC system, the rating drops to 65 kA Icu per UL 60947-4-1; at 600 V AC it holds at 15 kA Icu.

Mounts on a backplate in either horizontal or vertical orientation (flat on the back). The 140 mm width, 161 mm height, and 86 mm depth fit standard distribution panel cutouts. Front connections on both upside and downside simplify busbar and cable routing. The 35 mm connection pitch matches standard busbar systems. IP40 enclosure protection and IK07 impact resistance are sufficient for indoor panel environments; no additional sealing is required for dry locations.

Durability and duty

Mechanical durability is rated at 20000 cycles; electrical durability at 440 V In is 10000 cycles (20000 at In/2). At 690 V In, electrical durability drops to 5000 cycles. For a main breaker that cycles infrequently (once per shift or less), these figures are well within typical service life. For a switching duty that cycles multiple times per hour, the utilisation category A (non-frequent switching) applies — this is a distribution breaker, not a motor-starting contactor.

Frequently asked questions

What is the breaking capacity of the C25H6TM200 at 415 V?

70 kA Icu at 380/415 V AC 50/60 Hz conforming to IEC 60947-2. At 480 V AC the rating is 65 kA Icu per UL 60947-4-1.

What does the TM-D trip unit protect against?

The TM-D thermal-magnetic trip unit provides L protection (overload, thermal) and I protection (short-circuit, magnetic). It does not include earth-leakage protection.

What compliance documentation does Schneider provide for the C25H6TM200?

The breaker is certified to EN/IEC 60947-2 and UL 60947-4-1. It carries an IP40 rating per IEC 60529 and IK07 per IEC 62262. Pollution degree 3 and overvoltage category III per IEC 60664-1 are specified.

How do I get current pricing and availability for the C25H6TM200?