Schneider Electric C25R35E160 — Miniature Circuit Breakers (MCB)

Schneider Electric C25R35E160 ComPacT NSX 160A 3P MCCB, 200

MPNC25R35E160
Active

Schneider Electric ComPacT NSX, C25R35E160, 3P, 160 A at 40 °C, MicroLogic 5.2 E electronic trip unit, 200 kA Icu at 415 V AC, IEC 60947-2.

$1,829.47Ref. price · indicative, final on quote
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

C25R35E160 — Identification
ParameterValue
Product nameComPacT NSX
Product rangeComPacT
Product/component typeCircuit breaker
Device applicationDistribution
C25R35E160 — Ratings
ParameterValue
Rated current (In)160 A at 40 °C
Poles configuration3P
Breaking capacity200 kA Icu at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 200 kA Icu at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 200 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 80 kA Icu at 500 V AC 50/60 Hz conforming to IEC 60947-2 65 kA Icu at 525 V AC 50/60 Hz conforming to IEC 60947-2 45 kA Icu at 660/690 V AC 50/60 Hz conforming to IEC 60947-2
Rated service breaking capacity (Ics)200 kA at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 200 kA at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 200 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2 80 kA at 500 V AC 50/60 Hz conforming to IEC 60947-2 65 kA at 525 V AC 50/60 Hz conforming to IEC 60947-2 45 kA at 660/690 V AC 50/60 Hz conforming to IEC 60947-2
Rated operational voltage (Ue)690 V AC 50/60 Hz
Rated insulation voltage (Ui)800 V AC 50/60 Hz
Rated impulse withstand voltage (Uimp)8 kV
Network type (AC/DC)AC
Network frequency50/60 Hz
Utilisation categoryCategory A
Overvoltage categoryIII
C25R35E160 — Protection
ParameterValue
Trip unit technologyElectronic
Earth-leakage protectionWithout
Suitability for isolationYes conforming to EN/IEC 60947-2
Electrical durability (cycles)20000 cycles at 440 V In/2 10000 cycles at 440 V In 10000 cycles at 690 V In/2 5000 cycles at 690 V In
Mechanical durability (cycles)20000 cycles
C25R35E160 — Mechanical
ParameterValue
Mounting supportBackplate
Control typeToggle
Local signalling/indicationFlashing LED (green) for ready to operate LED 105 % Ir (red) for overload LED 90 % Ir (orange) for overload
C25R35E160 — Environmental
ParameterValue
Operating ambient temperature-25...70 °C
Storage ambient temperature-40...85 °C
IP degree of protectionIP40 conforming to IEC 60529
Pollution degree3 conforming to IEC 60664-1
Relative humidity0...95 %
C25R35E160 — Approvals
ParameterValue
StandardsEN/IEC 60947-2
C25R35E160 — Specifications
ParameterValue
[Ir] long-time protection pick-up adjustment range63...160 A
Trip unit protection functionsLSI

Product details

The C25R35E160 is a Schneider Electric ComPacT NSX250R molded-case circuit breaker, 3-pole, with an electronic MicroLogic 5.2 E trip unit rated 160 A at 40 °C. It provides LSI protection — long-time overload (L), short-time short-circuit (S), and instantaneous short-circuit (I) — plus energy metering and communication via the trip unit's LCD display.

The 160 A trip rating (at 40 °C) sets the continuous current capacity; for higher ambient temperatures or enclosed mounting, derate per the IEC 60947-2 thermal curve. The electronic MicroLogic 5.2 E trip unit adds thermal memory (20 min before and after tripping), energy metering, and communication of instantaneous and demand values, power quality, and time-stamped event histories, which simplifies downstream monitoring and diagnostics.

Connection pitch is 35 mm.

Frequently asked questions

Where can I buy C25R35E160 and get a price?

This part is sourced and quoted to order against an RFQ through independent distribution. Submit an RFQ for current pricing and availability.

What is the breaking capacity of C25R35E160?

The breaking capacity is 200 kA Icu at 415 V AC (also 200 kA at 240 V and 440 V, 80 kA at 500 V, 65 kA at 525 V, and 45 kA at 690 V) per IEC 60947-2.

What protection functions does the MicroLogic 5.2 E trip unit provide?

It provides L (long-time overload), S (short-time short-circuit), and I (instantaneous short-circuit) protection, plus energy metering and communication of power quality, demand values, and event histories.

MPN
C25R35E160