Skip to main content
Schneider Electric C25R36E100 — Residual Current Breakers (RCCB/RCBO)

Schneider Electric C25R36E100 ComPacT NSX 100A, 200kA, Micro

MPNC25R36E100
Obsolete

Schneider Electric ComPacT NSX, NSX250R, 3P, 100 A at 40 °C, 200 kA Icu at 415 V AC, MicroLogic 6.2 E electronic trip unit, LSI+G protection, energy metering, toggle control, LCD display.

$24.52Ref. price · indicative, final on quote
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

C25R36E100 — Residual Current Protection
ParameterValue
Trip unit technologyElectronic
Local signalling / indicationFlashing LED (green) for ready to operate LED 105 % Ir (red) for overload LED 90 % Ir (orange) for overload
C25R36E100 — Electrical Ratings
ParameterValue
Rated current (In)100 A at 40 °C
Rated operational voltage (Ue)690 V AC 50/60 Hz
Poles description3P
Network typeAC
Network frequency50/60 Hz
Rated insulation voltage (Ui)800 V AC 50/60 Hz
Rated impulse withstand voltage (Uimp)8 kV
Overvoltage categoryIII
Electrical durability20000 cycles at 440 V In/2 10000 cycles at 440 V In 10000 cycles at 690 V In/2 5000 cycles at 690 V In
Mechanical durability (operating cycles)20000 cycles
C25R36E100 — Identification
ParameterValue
Product nameComPacT NSX
Product / component typeCircuit breaker
Product range / familyComPacT
Device short nameNSX250R
C25R36E100 — Mechanical
ParameterValue
Mounting supportBackplate
Mounting positionHorizontal and vertical Flat on the back
Control typeToggle
C25R36E100 — Environmental
ParameterValue
Operating ambient temperature-25...70 °C
Storage ambient temperature-40...85 °C
IP degree of protectionIP40 conforming to IEC 60529
Pollution degree3 conforming to IEC 60664-1
Relative humidity0...95 %
Operating altitude0...2000 m without derating 2000 m...5000 m with derating
C25R36E100 — Approvals
ParameterValue
StandardsEN/IEC 60947-2

Product details

The C25R36E100 is a Schneider Electric ComPacT NSX250R frame circuit breaker with a MicroLogic 6.2 E electronic trip unit, rated 100 A at 40 °C. The 3-pole construction with front connections on both sides suits backplate mounting in standard switchgear enclosures.

Protection and metering in one unit

The MicroLogic 6.2 E trip unit packs four protection functions: L (long-time overload), S (short-time short-circuit), I (instantaneous short-circuit), and G (ground fault). That covers the full selectivity curve for a distribution feeder. On top of protection, the trip unit includes an energy meter — it logs instantaneous and demand values, time-stamped histories, event tables, power quality metrics, and protection/alarm settings. The LCD display and flashing LED indicators (green for ready, red at 105% Ir, orange at 90% Ir) give local status without a connected controller.

Integration notes

Mounts on a backplate in any orientation — horizontal, vertical, or flat. The 105 mm width, 161 mm height, and 86 mm depth fit standard panel cutouts for the NSX250R frame. Five accessory slots are available for communication modules, auxiliary contacts, or shunt trips.

Frequently asked questions

How do I get current pricing and availability for C25R36E100?

Submit an RFQ through this listing. Pricing and stock are confirmed at quote time through independent distribution channels.

What is the closest alternative to C25R36E100 in the ComPacT NSX family?

Within the same NSX250R frame, the closest alternative would be a different MicroLogic trip unit variant (e.g., MicroLogic 2.3 for thermal-magnetic protection without ground fault or metering). The frame, breaking capacity, and physical dimensions are identical; the trip unit and protection functions differ.

What compliance documentation does Schneider provide for C25R36E100?

The C25R36E100 is certified to EN/IEC 60947-2. The manufacturer provides a declaration of conformity and test reports for the breaking capacity ratings listed. RoHS and REACH compliance documentation is available on request.

MPN
C25R36E100