Skip to main content
Schneider Electric C25R46E250

Schneider C25R46E250 ComPacT NSX circuit breaker, 250 A, 4-pole, 200 kA

MPNC25R46E250
Active

Schneider C25R46E250 Compact Nsx, New Generation — now discontinued, supplied from remaining surplus and broker stock.

$23.85Ref. price · indicative, final on quote
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

C25R46E250 key specifications
ParameterValue
Control typeToggle
Display typeLCD display
Network typeAC
Protection typeL : for overload protection (long time) S : for short time short-circuit protection I : for instantaneous short-circuit protection G : for ground fault protection
Type of measurementEnergy meter
Product or component typeCircuit breaker
Long-time protection delay adjustment type trAdjustable
Short-time protection delay adjustment type tsdAdjustable 5 settings
Short-time protection pick-up adjustment type isdAdjustable
Ground-fault protection pick-up adjustment type igAdjustable 9 settings
Instantaneous protection pick-up adjustment type iiAdjustable
Ground-fault protection time delay adjustment type tgAdjustable 5 settings

All specifications

C25R46E250 additional specifications
ParameterValue
Long-time pick-up adjustment type ir (thermal protection)Adjustable 9 settings
Voltage800 V AC 50/60 Hz
[Ue] rated operational voltage690 V AC 50/60 Hz
[Uimp] rated impulse withstand voltage8 kV
Breaking capacity200 kA Icu at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 200 kA Icu at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 200 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 80 kA Icu at 500 V AC 50/60 Hz conforming to IEC 60947-2 65 kA Icu at 525 V AC 50/60 Hz conforming to IEC 60947-2 45 kA Icu at 660/690 V AC 50/60 Hz conforming to IEC 60947-2
Current250 A at 40 °C
Breaking capacity codeR 200 kA 415 V AC
[Ics] rated service breaking capacity200 kA at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 200 kA at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 200 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2 80 kA at 500 V AC 50/60 Hz conforming to IEC 60947-2 65 kA at 525 V AC 50/60 Hz conforming to IEC 60947-2 45 kA at 660/690 V AC 50/60 Hz conforming to IEC 60947-2
Power dissipation per pole17.6 W
Network frequency50/60 Hz
Poles description4P
Protected poles description4D 3D + OSN 3D + N/2 3D
Utilisation categoryCategory A
IK degree of protectionIK07 conforming to IEC 62262
IP degree of protectionIP40 conforming to IEC 60529
Communication of dataMaximeters/minimeters Power quality Demand current and power Protection and alarm settings Energy metering Time-stamped histories and event tables Instantaneous and demand values Maintenance indicators
Mounting supportBackplate
Mounting positionHorizontal and vertical Flat on the back
Circuit breaker mounting modeFixed
Connection pitch35 mm
Upside connectionFront
Downside connectionFront
Pollution degree3 conforming to IEC 60664-1
Relative humidity0...95 %
Operating altitude0...2000 m without derating 2000 m...5000 m with derating
Electrical shock protection classClass II on front face
Depth86 mm
Width140 mm
Height161 mm
Electrical durability20000 cycles at 440 V In/2 10000 cycles at 440 V In 10000 cycles at 690 V In/2 5000 cycles at 690 V In
Mechanical durability20000 cycles
StandardsEN/IEC 60947-2
RangeComPacT
Thermal memory20 minutes before and after tripping
Trip unit nameMicroLogic 6.2 E
Number of slots5 slot(s)
Local signallingFlashing LED (green) for ready to operate LED 105 % Ir (red) for overload LED 90 % Ir (orange) for overload
Neutral positionLeft
Trip unit rating250 A at 40 °C
Device short nameNSX250R
Device applicationDistribution
Overvoltage categoryIII
Trip unit technologyElectronic
Earth-leakage protectionWithout
Suitability for isolationYes conforming to EN/IEC 60947-2
Neutral protection setting0.5 x Ir (3D + N/2) 1 x Ir (4D) 1.6 x Ir (3D + OSN) No protection (3D)
Trip unit protection functionsLSIG
Zone selective interlocking ZSIWith
Ambient air temperature for storage-40...85 °C
Ambient air temperature for operation-25...70 °C
[Tr] Long-Time delay adjustment range15...400 s at 1.5 x Ir 0.5...16 s at 6 x Ir 0.35...11 s at 7.2 x Ir
[Tsd] Short-Time delay adjustment range0...0.4 s I²t=off 0.1...0.4 s I²t=on
[Ig] ground-fault pick-up adjustment range0.4...1 x In for In = 40 A 0.2...1 x In for In > 40 A Ig enable on/off
[tg] ground-fault time delay adjustment range0...0.4 s I²t=off 0.1...0.4 s I²t=on
[Ir] long-time protection pick-up adjustment range100...250 A
[Isd] short-time protection pick-up adjustment range1.5...10 x Ir
[Ii] instantaneous protection pick-up adjustment range1.5...12 x In

Product details

Overview

The C25R46E250 is a Schneider ComPacT NSX molded case circuit breaker rated 250 A continuous, 4-pole, with a 200 kA ICu breaking capacity at 690 V AC. It carries the MicroLogic 6.2 E electronic trip unit providing LSI and ground-fault protection, and is in active production under IEC 60947-2.

MPN
C25R46E250