Specifications

C25S4D — Identification
ParameterValue
Product / component typeBasic frame
Device applicationDistribution
C25S4D — Electrical
ParameterValue
[In] rated current250 A at 40 °C
Breaking capacity100 kA Icu at 250 V DC 1P conforming to IEC 60947-2 100 kA Icu at 24...125 V DC 1P conforming to IEC 60947-2 100 kA Icu at 500 V DC 2P conforming to IEC 60947-2 100 kA Icu at 750 V DC 3P conforming to IEC 60947-2
[Ics] rated service breaking capacity100 kA at 250 V DC conforming to IEC 60947-2 (1P) 100 kA at 24...125 V DC conforming to IEC 60947-2 (1P) 100 kA at 500 V DC conforming to IEC 60947-2 (2P) 100 kA at 750 V DC conforming to IEC 60947-2 (3P)
[Ue] rated operational voltage750 V DC conforming to IEC 60947-2
[Ui] rated insulation voltage750 V DC conforming to IEC 60947-2
C25S4D — Specifications
ParameterValue
Poles description4P
Device short nameNSX250S DC
StandardsEN/IEC 60947-2

Product details

The Schneider Electric C25S4D is a ComPacT NSX250S DC basic frame — a 4-pole, 250 A molded-case circuit breaker rated for DC distribution networks up to 750 V DC. It delivers 100 kA Icu breaking capacity across the full voltage range (250 V DC 1P through 750 V DC 3P), certified to EN/IEC 60947-2. This is the frame only; it ships without a trip unit, so you select the protection module (electronic or thermal-magnetic) separately to match the load's coordination curve.

For a 250 A frame on a 750 V DC bus, that SCCR headroom covers most industrial battery banks, UPS outputs, and DC traction supplies. The 10 ms maximum breaking time means the arc is quenched fast enough to limit let-through energy for downstream components. The IP40 front face and IK07 impact resistance handle panel-side handling and accidental tool contact, but the backplate mount and fixed design are meant for permanent installation, not portable gear.

Fixed backplate mount, front connection both top and bottom. The 140 mm width, 161 mm height, and 86 mm depth fit a standard MCCB footprint on a backplate or sub-panel. Neutral is on the left; the toggle control gives clear visual indication of the contact position.

Frequently asked questions

Where can I buy C25S4D?

The C25S4D is sourced to order against an RFQ through independent distribution; availability and current pricing are confirmed at quote time.