Schneider Electric C25W3TM250 — Miniature Circuit Breakers (MCB)

Schneider C25W3TM250 ComPacT NSX circuit breaker, 250 A, 100 kA Icu

MPNC25W3TM250
Obsolete

Schneider Electric ComPacT NSX C25W3TM250 molded case circuit breaker, 3-pole, 250 A, 100 kA Icu at 690 V AC, thermal-magnetic TM-D trip unit, fixed mount, toggle control, IEC 60947-2.

$6.74Ref. price · indicative, final on quote
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

C25W3TM250 — Identification
ParameterValue
Product nameComPacT NSX
Product rangeComPacT
Product/component typeCircuit breaker
Device applicationDistribution
C25W3TM250 — Ratings
ParameterValue
Rated current (In)250 A at 40 °C
Poles configuration3P
Breaking capacity100 kA Icu at 500 V AC 50/60 Hz conforming to IEC 60947-2 100 kA Icu at 525 V AC 50/60 Hz conforming to IEC 60947-2 100 kA Icu at 660/690 V AC 50/60 Hz conforming to IEC 60947-2
Rated service breaking capacity (Ics)100 kA at 500 V AC 50/60 Hz conforming to IEC 60947-2 100 kA at 525 V AC 50/60 Hz conforming to IEC 60947-2 100 kA at 660/690 V AC 50/60 Hz conforming to IEC 60947-2
Rated operational voltage (Ue)690 V AC 50/60 Hz
Rated insulation voltage (Ui)800 V AC 50/60 Hz
Rated impulse withstand voltage (Uimp)8 kV
Network type (AC/DC)AC
Network frequency50/60 Hz
Utilisation categoryCategory A
Overvoltage categoryIII
C25W3TM250 — Protection
ParameterValue
Trip unit technologyThermal-magnetic
Earth-leakage protectionWithout
Suitability for isolationYes conforming to EN/IEC 60947-2
Electrical durability (cycles)20000 cycles at 440 V In/2 10000 cycles at 440 V In 10000 cycles at 690 V In/2 5000 cycles at 690 V In
Mechanical durability (cycles)20000 cycles
C25W3TM250 — Mechanical
ParameterValue
Mounting supportBackplate
Control typeToggle
C25W3TM250 — Environmental
ParameterValue
Operating ambient temperature-25...70 °C
Storage ambient temperature-50...85 °C
IP degree of protectionIP40 conforming to IEC 60529
Pollution degree3 conforming to IEC 60664-1
Relative humidity0...95 %
C25W3TM250 — Approvals
ParameterValue
StandardsEN/IEC 60947-2
C25W3TM250 — Specifications
ParameterValue
[Ir] long-time protection pick-up adjustment range0.7...1 x In
Trip unit protection functionsLI

Product details

Overview

The C25W3TM250 is a Schneider ComPacT NSX molded case circuit breaker rated 250 A continuous with a 100 kA Icu breaking capacity at 690 V AC, built for distribution duty on a 3-pole fixed mount.

MPN