The 3-pole design (3P) and 100 kA Icu at 500 V AC (50/60 Hz) per IEC 60947-2 mean it can safely interrupt fault currents up to 100 kA without upstream cascading — critical for high-fault-capacity distribution panels where selectivity with upstream devices is required. The thermal-magnetic trip provides L (overload) and I (short-circuit) protection in one unit, so you get both time-delayed thermal response and instantaneous magnetic trip without a separate relay. Rated for 125 A continuous at 40 °C. Breaking capacity holds at 100 kA Icu across 500 V, 525 V, and 660/690 V AC. IP40 front face and IK07 impact resistance suit indoor panel environments where accidental tool drops or panel-door impacts are a risk.
Sourcing and lifecycle — what to expect when you order
IP40 and IK07 ratings are factory-tested per IEC 60529 and IEC 62262 respectively.
Connection pitch is 35 mm. Mechanical durability is rated at 20,000 cycles; electrical durability varies by load: 20,000 cycles at 440 V at half rated current (In/2), 10,000 cycles at 440 V at full In, and 5,000 cycles at 690 V at full In. The toggle control is manual only — no motor operator or shunt trip is integrated in this base variant.