Skip to main content
Schneider Electric C25W42D160

Schneider Electric C25W42D160

MPNC25W42D160
Active

Circuit breaker ComPacT NSX250HB2. 100kA at 690VAC. MicroLogic 2.2 trip unit 160A. 4 poles 4d

$1,004.43Ref. price · indicative, final on quote
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

C25W42D160 key specifications
ParameterValue
Control typeToggle
Network typeAC
Protection typeL : for overload protection (long time) So : for short time short-circuit protection with fixed delay I : for instantaneous short-circuit protection
Product or component typeCircuit breaker
Long-time protection delay adjustment type trFixed
Short-time protection delay adjustment type tsdFixed
Short-time protection pick-up adjustment type isdAdjustable 9 settings
Instantaneous protection pick-up adjustment type iiFixed
Long-time pick-up adjustment type ir (thermal protection)Adjustable 9 settings
Voltage800 V AC 50/60 Hz
[Ue] rated operational voltage690 V AC 50/60 Hz
[Uimp] rated impulse withstand voltage8 kV

All specifications

C25W42D160 additional specifications
ParameterValue
Breaking capacity100 kA Icu at 500 V AC 50/60 Hz conforming to IEC 60947-2 100 kA Icu at 525 V AC 50/60 Hz conforming to IEC 60947-2 100 kA Icu at 660/690 V AC 50/60 Hz conforming to IEC 60947-2
Current160 A at 40 °C
Breaking capacity codeHB2 100 kA 690 V AC
[Ics] rated service breaking capacity100 kA at 500 V AC 50/60 Hz conforming to IEC 60947-2 100 kA at 525 V AC 50/60 Hz conforming to IEC 60947-2 100 kA at 660/690 V AC 50/60 Hz conforming to IEC 60947-2
Power dissipation per pole17.6 W
Network frequency50/60 Hz
Poles description4P
Protected poles description4D 3D + N/2 3D
Utilisation categoryCategory A
IK degree of protectionIK07 conforming to IEC 62262
IP degree of protectionIP40 conforming to IEC 60529
Mounting supportBackplate
Mounting positionHorizontal and vertical Flat on the back
Circuit breaker mounting modeFixed
Connection pitch35 mm
Upside connectionFront
Downside connectionFront
Pollution degree3 conforming to IEC 60664-1
Relative humidity0...95 %
Operating altitude0...2000 m without derating 2000 m...5000 m with derating
Electrical shock protection classClass II on front face
Depth86 mm
Width140 mm
Height161 mm
Product weight2.8 kg
Electrical durability20000 cycles at 440 V In/2 10000 cycles at 440 V In 10000 cycles at 690 V In/2 5000 cycles at 690 V In
Mechanical durability20000 cycles
StandardsEN/IEC 60947-2
RangeComPacT
Thermal memory20 minutes before and after tripping
Trip unit nameMicroLogic 2.2
Number of slots5 slot(s)
Local signallingFlashing LED (green) for ready to operate LED 105 % Ir (red) for overload LED 90 % Ir (orange) for overload
Neutral positionLeft
Trip unit rating160 A at 40 °C
Device short nameNSX250HB2
Device applicationDistribution
Overvoltage categoryIII
Trip unit technologyElectronic
Earth-leakage protectionWithout
Suitability for isolationYes conforming to EN/IEC 60947-2
Neutral protection setting0.5 x Ir (3D + N/2) 1 x Ir (4D) No protection (3D)
Trip unit protection functionsLSoI
Zone selective interlocking ZSIWithout
Ambient air temperature for storage-50...85 °C
Ambient air temperature for operation-25...70 °C
[Tr] Long-Time delay adjustment range400 s at 1.5 x Ir 16 s at 6 x Ir 11 s at 7.2 x Ir
[Ir] long-time protection pick-up adjustment range63...160 A
[Isd] short-time protection pick-up adjustment range1.5...10 x Ir
[Ii] instantaneous protection pick-up adjustment range2400 A
MPN