Control unit MicroLogic 2.0E, ComPacT NS630b to NS1600 withdrawable and manually operated, basic protections

$2,388.96Ref. price · indicative, final on quote
Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

C2EWM key specifications
ParameterValue
Display typeDigital display
Network typeAC
Protection typeL : for overload protection (long time) I : for instantaneous short-circuit protection
Range of productComPacT NS630b...1600 new generation
Type of measurementEnergy meter
Product or component typeControl unit
Long-time protection delay adjustment type trAdjustable 9 settings
Instantaneous protection pick-up adjustment type iiAdjustable 9 settings
Long-time pick-up adjustment type ir (thermal protection)Adjustable 9 settings
Network frequency50/60 Hz
Poles4P 3P
Protected poles description4t 3t 3t + N/2

All specifications

C2EWM additional specifications
ParameterValue
Communication of dataMeasurement readout Protection and alarm settings
Circuit breaker mounting modeWithdrawable
StandardsIEC 60947-4-2
RangeComPacT
Thermal memory20 mn
Trip unit nameMicroLogic 2.0 E
Local signalling3 LEDs (red) for electrical fault 1 LED (red) for internal error 1 LED (yellow) for overload
Trip unit rating630 A at 50 °C 800 A at 50 °C 1000 A at 50 °C 1250 A at 50 °C 1600 A at 50 °C
Device applicationDistribution
Trip unit technologyElectronic
Earth-leakage protectionWithout
Trip unit protection functionsBasic protection
Zone selective interlocking ZSIWithout
Ambient air temperature for storage-25...85 °C
Ambient air temperature for operation-25...70 °C
[Tr] Long-Time protection delay adjustment range0.7...16.6 s at 7.2 x Ir 0.7...24 s at 6 x Ir 12.5...600 s at 1.5 x Ir
[Ir] long-time protection pick-up adjustment range0.4...1 x In
[Ii] instantaneous protection pick-up adjustment range1.5...10 x Ir
MPN