Schneider Electric C60FM — Molded Case Circuit Breakers (MCCB)

Schneider Electric C60FM MicroLogic 6.0 Control Unit, ComPac

MPNC60FM
Active

Schneider Electric, ComPacT NS630b–NS3200, MicroLogic 6.0 control unit, 630–3200 A, selective + earth-fault protection, IEC 60947-4-2.

$861.37Ref. price · indicative, final on quote
Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

C60FM — Identification
ParameterValue
Product / component typeControl unit
Device applicationDistribution
C60FM — Ratings
ParameterValue
Number of poles3P 4P
C60FM — Specifications
ParameterValue
Trip unit nameMicroLogic 6.0
Trip unit technologyElectronic
StandardsIEC 60947-4-2

Product details

MicroLogic 6.0 control unit for ComPacT NS630b–NS3200

The C60FM is the MicroLogic 6.0 electronic control unit for Schneider Electric's ComPacT NS630b–NS3200 new-generation air circuit breakers. It provides selective (L, S, I) plus earth-fault (G) protection, with the trip unit rating adjustable from 630 A up to 3200 A at 50 °C. The unit is designed for fixed-mounted breakers on 50/60 Hz AC distribution networks.

Protection settings and adjustability

Long-time pickup (Ir) is adjustable over 0.4–1.0 x In in nine steps, with delay (tr) settable from 0.7–16.6 s at 7.2 x Ir or 12.5–600 s at 1.5 x Ir. Short-time pickup (Isd) covers 1.5–10 x Ir, also nine steps, with delay (tsd) 0–0.4 s (I²t on or off). Instantaneous pickup (Ii) is adjustable from 2–15 x In, or can be switched off entirely. Earth-fault pickup (Ig) ranges from 0.2–1.0 x In (for In ≤ 1250 A), delay (tg) 0–0.4 s (I²t on or off). All adjustments are made via the front-panel dials — no software or programming tool is required.

Status and fault signalling

Three red LEDs indicate the type of electrical fault (overload, short-circuit, earth fault); a separate red LED flags an internal trip-unit error, and a yellow LED signals an overload pre-alarm. The thermal memory (20-minute time constant) retains the thermal state after a trip, preventing immediate reclosure onto a still-hot conductor.

Rated per IEC 60947-4-2, the standard for circuit-breaker control units. The unit is designed for distribution applications and supports 3-pole, 4-pole, and 3-pole + half-neutral (3t + N/2) configurations.

Frequently asked questions

Where can I buy C60FM and how do I get a price?

The C60FM is sourced to order against an RFQ through independent distribution. Submit a request for quote (RFQ) to confirm current availability and pricing.

What is C60FM's listed range (ComPacT) on this component line?

The C60FM belongs to the ComPacT range, specifically the ComPacT NS630b–NS1600 new generation and ComPacT NS1600b–NS3200 new generation series.

What is C60FM's listed standards (IEC 60947-4-2) on this component line?

The C60FM is certified to IEC 60947-4-2, the standard for control units of circuit-breakers used in distribution networks.