Skip to main content
Schneider Electric C60HB101

Schneider Electric C60HB101

MPNC60HB101
Obsolete

C60HB101 - MINIATURE CIRCUIT BREAKER by MERLIN GERIN

$47.59Ref. price · indicative, final on quote
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

C60HB101 key specifications
ParameterValue
Control typeToggle
Network typeAC DC
Product or component typeMiniature circuit-breaker
Voltage500 V AC 50/60 Hz conforming to IEC 60947-2
[Ue] rated operational voltage12...440 V AC 50/60 Hz
[Uimp] rated impulse withstand voltage6 kV conforming to IEC 60947-2
Breaking capacity10 kA Icn at 230/400 V AC 50/60 Hz conforming to EN 60898 15 kA Icu at 230...240 V AC 50/60 Hz conforming to IEC 60947-2 20 kA Icu at 60 V DC 1P conforming to IEC 60947-2 30 kA Icu at 130 V AC 50/60 Hz conforming to IEC 60947-2 4 kA Icu at 400...415 V AC 50/60 Hz conforming to IEC 60947-2
Current1 A at 30 °C
[Ics] rated service breaking capacity2 kA conforming to IEC 60947-2 - 400...415 V AC 50/60 Hz 25 kA conforming to IEC 60947-2 - 130 V AC 50/60 Hz 7.5 kA conforming to IEC 60947-2 - 230...240 V AC 50/60 Hz 7.5 kA conforming to EN 60898 - 230/400 V AC 50/60 Hz
Network frequency50/60 Hz
Poles description1P
Number of protected poles1

All specifications

C60HB101 additional specifications
ParameterValue
Mounting modeFixed
Mounting support35 mm symmetrical DIN rail
Connections - terminalsTunnel type terminals16 mm² flexible Tunnel type terminals25 mm² rigid
Relative humidity95 % at 55 °C
Operating altitude2000 m
Depth73 mm
Width18 mm
Height81 mm
Mechanical durability20000 cycles
StandardsEN 60898 IEC 60947-2
RangeMulti9
Curve codeB
9 mm pitches2
Tropicalisation2 conforming to IEC 60068-1
Limitation class3 conforming to IEC 60947-2
Local signallingON/OFF indication
Device short nameC60H
Tightening torquePower circuit: 2 N.m upside 2 N.m downside
Device applicationDistribution
Trip unit technologyThermal-magnetic
Magnetic tripping limit3...5 x In
Suitability for isolationYes conforming to IEC 60947-2
Contact position indicatorYes
Ambient air temperature for storage-40...70 °C
Ambient air temperature for operation-25...60 °C
Comb busbar and distribution block compatibilityNO
MPN
C60HB101