Specifications
| Parameter | Value |
|---|---|
| Control type | Toggle |
| Network type | AC DC |
| Product or component type | Miniature circuit-breaker |
| Voltage | 500 V AC 50/60 Hz conforming to IEC 60947-2 |
| [Ue] rated operational voltage | 12...440 V AC 50/60 Hz |
| [Uimp] rated impulse withstand voltage | 6 kV conforming to IEC 60947-2 |
| Breaking capacity | 10 kA Icn at 230/400 V AC 50/60 Hz conforming to EN 60898 15 kA Icu at 230...240 V AC 50/60 Hz conforming to IEC 60947-2 20 kA Icu at 60 V DC 1P conforming to IEC 60947-2 30 kA Icu at 130 V AC 50/60 Hz conforming to IEC 60947-2 4 kA Icu at 400...415 V AC 50/60 Hz conforming to IEC 60947-2 |
| Current | 1 A at 30 °C |
| [Ics] rated service breaking capacity | 2 kA conforming to IEC 60947-2 - 400...415 V AC 50/60 Hz 25 kA conforming to IEC 60947-2 - 130 V AC 50/60 Hz 7.5 kA conforming to IEC 60947-2 - 230...240 V AC 50/60 Hz 7.5 kA conforming to EN 60898 - 230/400 V AC 50/60 Hz |
| Network frequency | 50/60 Hz |
| Poles description | 1P |
| Number of protected poles | 1 |
All specifications
| Parameter | Value |
|---|---|
| Mounting mode | Fixed |
| Mounting support | 35 mm symmetrical DIN rail |
| Connections - terminals | Tunnel type terminals16 mm² flexible Tunnel type terminals25 mm² rigid |
| Relative humidity | 95 % at 55 °C |
| Operating altitude | 2000 m |
| Depth | 73 mm |
| Width | 18 mm |
| Height | 81 mm |
| Mechanical durability | 20000 cycles |
| Standards | EN 60898 IEC 60947-2 |
| Range | Multi9 |
| Curve code | B |
| 9 mm pitches | 2 |
| Tropicalisation | 2 conforming to IEC 60068-1 |
| Limitation class | 3 conforming to IEC 60947-2 |
| Local signalling | ON/OFF indication |
| Device short name | C60H |
| Tightening torque | Power circuit: 2 N.m upside 2 N.m downside |
| Device application | Distribution |
| Trip unit technology | Thermal-magnetic |
| Magnetic tripping limit | 3...5 x In |
| Suitability for isolation | Yes conforming to IEC 60947-2 |
| Contact position indicator | Yes |
| Ambient air temperature for storage | -40...70 °C |
| Ambient air temperature for operation | -25...60 °C |
| Comb busbar and distribution block compatibility | NO |