Skip to main content
Schneider Electric C60HC16R100 — Residual Current Breakers (RCCB/RCBO)

C60HC16R100 C60H RCBO 1P+N 16A C-Curve 10kA

MPNC60HC16R100
Obsolete

Schneider Electric C60H RCBO, 1 pole + N, 16 A, C curve, 10 kA breaking capacity, 100 mA earth leakage, obsolete.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

C60HC16R100 — Residual Current Protection
ParameterValue
Earth-leakage sensitivity (IΔn)100 mA
Earth-leakage protection class / typeClass AC
Earth-leakage trip time delayInstantaneous
Trip unit technologyThermal-magnetic
Local signalling / indicationPositive break indication
C60HC16R100 — Electrical Ratings
ParameterValue
Rated current (In)16 A at 30 °C
Rated operational voltage (Ue)50...250 V AC 50/60 Hz
Poles description1P + N
Neutral pole positionRight
Network typeAC
Network frequency50/60 Hz
Device location in systemOutgoer
Electrical durability20000 cycles
C60HC16R100 — Identification
ParameterValue
Device short nameC60H RCBO
C60HC16R100 — Mechanical
ParameterValue
Mounting support35 mm symmetrical DIN rail
Control typeToggle
Width in 9 mm modules2
Terminal connectionsTunnel type terminals (downstream) 10 mm² flexible Tunnel type terminals (downstream) 16 mm² rigid Tunnel type terminals (upstream) 16 mm² flexible Tunnel type terminals (upstream) 25 mm² rigid
Terminal tightening torque2 N.m
C60HC16R100 — Environmental
ParameterValue
Relative humidity95 % at 55 °C
Operating altitude2000 m
Tropicalisation2
C60HC16R100 — Approvals
ParameterValue
StandardsIEC 1009-2-2

Product details

The C60HC16R100 is a C60H-series RCBO (residual-current circuit breaker with overcurrent protection) from Schneider Electric, combining a 16 A thermal-magnetic MCB with 100 mA earth-leakage protection in a single 1P+N module. It is rated for 10 kA breaking capacity at 50–250 V AC, 50/60 Hz, conforming to IEC 1009-2-2. The C-curve (magnetic trip 5–10 × In) suits mixed inductive and resistive loads in distribution boards.

The 1P+N format occupies a single module width (9 mm pitch, 2 pitches total). The neutral is on the right side of the module. Positive-break indication confirms contact status visually.

The 100 mA earth-leakage sensitivity (Class AC, instantaneous) provides protection against leakage to earth for sinusoidal AC fault currents; it is not suitable for pulsed DC or high-frequency leakage. The thermal-magnetic trip unit handles overloads (thermal) and short-circuits (magnetic). Electrical durability is rated at 20,000 cycles.

Frequently asked questions

Where can I buy C60HC16R100?

We source the C60HC16R100 through independent distribution channels. Submit an RFQ for current availability and pricing — confirmed at quote time.

What are the key ratings of C60HC16R100?

16 A rated current, C-curve (5–10 × In magnetic trip), 10 kA breaking capacity at 50–250 V AC, 100 mA earth-leakage sensitivity (Class AC, instantaneous), 1P+N configuration, thermal-magnetic trip, 20,000-cycle electrical durability.

What standard does C60HC16R100 comply with?

It conforms to IEC 1009-2-2, which covers residual-current operated circuit breakers with integral overcurrent protection. It also meets EN 60898 for limitation class 3.

MPN