It combines a 32 A thermal-magnetic MCB with a 100 mA instantaneous earth-leakage protection module in a single DIN-rail unit. Rated operational voltage spans 50 to 250 V AC at 50/60 Hz, with a breaking capacity of 10 kA Icu per IEC 1009-2-2. The 3 kA limitation class per EN 60898 means it limits let-through energy under fault conditions, protecting downstream wiring. The unit is designed as an outgoer in distribution boards, with tunnel-type terminals accepting up to 25 mm² rigid upstream and 16 mm² rigid downstream.
The neutral is on the right side of the module. Terminal torque spec is 2 N·m. The positive break indication on the toggle gives a visible air gap when switched off — useful for lockout verification during panel maintenance.