The Schneider C60HC32RA30 is a 1P+N RCBO from the C60H series, combining overcurrent protection with 30 mA earth-leakage detection in a single DIN-rail module. Rated 32 A at 30 °C with a C-curve (magnetic trip 5-10 x In), it interrupts faults up to 10 kA Icu at 50-250 V AC. The 30 mA sensitivity covers additional protection against direct contact in final circuits — Class A, instantaneous trip, no intentional time delay. Positive break indication confirms contact separation for troubleshooting.
This order code is listed as obsolete by Schneider Electric. No official successor is provided in the available records.
Designed to IEC 1009-2-2 and EN 60898 (limitation class 3). The C-curve characteristic (5-10 x In) is the standard choice for general distribution circuits with moderate inrush — motor-starter or capacitive loads that draw more than a B-curve allows but less than a D-curve demands. The Class A earth-leakage detection responds to sinusoidal AC residual currents and pulsating DC waveforms. Tropicalisation treatment (2) supports operation in humid environments up to 95 % RH at 55 °C, at altitudes up to 2000 m.