Schneider Electric C60WM — Molded Case Circuit Breakers (MCCB)

Schneider Electric C60WM MicroLogic 6.0 Control Unit, 630-16

MPNC60WM
Active

Schneider Electric ComPacT NS630b-1600, MicroLogic 6.0 control unit, electronic trip, 630-1600 A at 50 °C, IEC 60947-4-2.

$4,209.84Ref. price · indicative, final on quote
Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

C60WM — Identification
ParameterValue
Product / component typeControl unit
Device applicationDistribution
C60WM — Ratings
ParameterValue
Number of poles3P 4P
C60WM — Specifications
ParameterValue
Trip unit nameMicroLogic 6.0
Trip unit technologyElectronic
StandardsIEC 60947-4-2

Product details

MicroLogic 6.0 control unit for ComPacT NS630b-1600

The Schneider Electric C60WM is a MicroLogic 6.0 electronic control unit for the ComPacT NS630b-1600 new generation withdrawable circuit breakers. It provides selective (S) and earth-fault (G) protection on top of the standard long-time (L) and instantaneous (I) functions — the LSI+G protection suite. Rated for trip unit currents from 630 A up to 1600 A at 50 °C, this is the brain that decides when the breaker opens and how fast.

What the protection settings mean on the line

The long-time pickup (Ir) adjusts from 0.4 to 1.0 x In across nine settings, with a thermal memory that holds the heat profile for 20 minutes — critical for motor starts where the second start sees a warmer conductor. Short-time pickup (Isd) spans 1.5 to 10 x Ir, also nine settings, with delay adjustable 0 to 0.4 s (I²t on or off). Instantaneous pickup (Ii) goes 2 to 15 x In, and can be switched Off entirely for selective coordination downstream. Ground-fault pickup (Ig) adjusts from 0.2 to 1.0 x In (for 400 A < In < 1250 A), with delay matching the short-time range. All of this means the unit can be dialed in for a specific feeder's coordination study — not just a fixed curve.

This control unit is designed for the withdrawable version of the ComPacT NS630b-1600 frame. That means the breaker chassis stays wired to the bus; the cradle-mounted unit slides in and out for testing or swap without disturbing the main power connections. The protected poles config is 4t, 3t, or 3t + N/2 — covers three- and four-pole arrangements. Local signaling uses three red LEDs for electrical faults, one red for internal error, one yellow for overload. No zone-selective interlocking (ZSI) on this variant.

Frequently asked questions

What is C60WM's listed range and standards?

The C60WM belongs to the ComPacT NS630b-1600 new generation range and is designed to IEC 60947-4-2, the standard for contactors and motor-starters with integral overload protection.

What protection functions does the MicroLogic 6.0 control unit provide?

The MicroLogic 6.0 provides long-time (L) overload, short-time (S) selective short-circuit, instantaneous (I) short-circuit, and ground-fault (G) earth-leakage protection — the LSI+G suite. All pickup and delay settings are field-adjustable.

Where can I buy the C60WM and what is the lead time?

The C60WM is sourced and quoted to order against an RFQ through independent distribution channels. Availability and current pricing are confirmed at quote time — submit an RFQ for a firm lead time.