Skip to main content
Schneider Electric C6345E630

Schneider C6345E630 Breaker Accessory

MPNC6345E630
Active

C6345E630 by SQUARE D

StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026
How we verify every order →

Specifications

C6345E630 key specifications
ParameterValue
Display typeLCD display
Network typeAC
Protection typeL : for overload protection (long time) S : for short time short-circuit protection I : for instantaneous short-circuit protection
Range of productComPacT NSX400...630
Type of measurementEnergy meter
Product or component typeTrip unit
Long-time protection delay adjustment type trAdjustable
Short-time protection delay adjustment type tsdAdjustable
Short-time protection pick-up adjustment type isdAdjustable 9 settings
Instantaneous protection pick-up adjustment type iiAdjustable
Long-time pick-up adjustment type ir (thermal protection)Adjustable 9 settings
[Ue] rated operational voltage690 V AC 50/60 Hz

All specifications

C6345E630 additional specifications
ParameterValue
Network frequency50/60 Hz
Poles description4P
Protected poles description3D + N/2 4D 3D + OSN 3D
IP degree of protectionIP40 conforming to IEC 60529
Communication of dataEnergy metering Protection and alarm settings Time-stamped histories and event tables Instantaneous and demand values Maintenance indicators Demand current and power Power quality Maximeters/minimeters
Circuit breaker mounting modeFixed
Pollution degree3 conforming to IEC 60947-1
Electrical shock protection classClass II
StandardsEN/IEC 60947-2
RangeComPacT
Thermal memory20 minutes before and after tripping
Trip unit nameMicroLogic 5.3 E
Local signallingFlashing LED (green) for ready to operate LED 105 % Ir (red) for overload LED 90 % Ir (orange) for overload
Neutral positionLeft
Trip unit rating630 A at 40 °C
Device applicationDistribution
Trip unit technologyElectronic
Earth-leakage protectionWithout
Electrical data recordingMaintenance indicators
Neutral protection settings0.5 x Ir (3D + N/2) 1 x Ir (4D) 1.6 x Ir (3D + OSN) No protection (3D)
Trip unit protection functionsLSI
Zone selective interlocking ZSIWith
Ambient air temperature for storage-40...85 °C
Ambient air temperature for operation-25...70 °C
[Tr] Long-Time protection delay adjustment range15...400 s at 1.5 x Ir 0.35...11 s at 7.2 x Ir 0.5...16 s at 6 x Ir
[Ir] long-time protection pick-up adjustment range250...630 A
[tsd] short-time protection delay adjustment range0...0.4 s I²t=off 0.1...0.4 s I²t=on
[Isd] short-time protection pick-up adjustment range1.5...10 x Ir
[Ii] instantaneous protection pick-up adjustment range1.5...11 x In
MPN